Model: LC5296-XP-DC
Doc. Ref. no.:- m61D/om/401
Issue no. 05
User’s Manual
Page 26 of 31
22
Password
40034
Int
R + W
23
Control Set point-1
40035
Int
R + W
24
Control Set Point-2
40036
Int
R + W
25
Set Value 2
40037
Int
R + W
26
Input Type-2
40038
Int
R + W
27
Zero-2
40039
Int
R + W
29
Span-2
40040
Int
R + W
30
Decimal Point-2
40041
Int
R + W
31
Relay-1 Map
40042
Int
R + W
32
Relay-2 Map
40043
Int
R + W
33
Retransmission-1 Map
40044
Int
R + W
34
Retransmission-2 Map
40045
Int
R + W
35
Serial Input PV 1
40046
Int
R + W
36
Serial Input PV 2
40047
int
R + W
37
Time out
40048
Unsigned
char
R + W
38
PV after Time out
0: holds Last PV,
1: PV shows "----"
40049
Unsigned
char
R + W
9.3 Exceptional Response
CODE
MEANING
01
Function code Invalid. It must be 01, 05, 03 or 06.The function code received in
the query is not allowable action for the slave.
02
Illegal address value. The data address received in the query is not an allowable
address for the salve.
03
Illegal data value. A value contained in the query data field is not an allowable
value for the salve.
06
When Master device write some parameters to Slave device, If slave device busy
then it will send 06 code to indicate slave device is busy.
Note:
1. Any Parameter which is not available for the Model, the value at its
address will be “0”. And it is Not Writable.
2. If some parameters are blocked in the Menu due to particular
Configuration Settings, value at their respective address will be “0”. And
these are Not Writable.
(EX: If device’s Input type is currently RTD.1, so DP (Decimal Point)
parameter will not available in the Menu. So at its Address (40011) value will
be “0” & it can’t changeable.)