Model: LC5296-XP-DC
Doc. Ref. no.:- m61D/om/401
Issue no.: 05
User’s Manual
Page 19 of 31
C1.sp
/
C2.sp
0 : C1.SP (Control Set Point 1)
1 : C2.SP (Control Set Point 2)
BRHT
(
brHt
)
Brightness
Adjust Brightness of the 7-segment Display.
10 to 100
100
SR.NO
(
sr.no
)
Serial No.
Unit ID for Modbus-RS485 Communication
1 to 247
1
Device
supports
RS485
Communicati
on.
BAUD
(
baud
)
Baud Rate
Set Modbus RS485 Communication Baud
Rate
9600
/
19.2k
/
38.4k
0 : 9600 (9600 bps)
1 : 19.2K (19200 bps)
2 : 38.4K (38400 bps)
9600
Device
supports
RS485
Communicati
on.
RTR.1
(
rtr.1
)
Retransmissio
n 1 Type
Retransmission-1 Output Type
This output is according to PV input.
Zero & Span acts as Min & Max value of
retransmission o/p scale respectively.
0-5v
/
1-5v
/
0-10v
/
4-20
/
0-20
0 : 0-5V
1 : 1-5V
2 : 0-10V
3 : 4-20mA
4 : 0-20mA
Voltage or Current is Jumper Selectable
from the Hardware.
4-20
Device
Supports
Retransmissi
on Output.
RT.D.1
(
rt.D.1
)
Retransmissio
n-1 Direction
Set Direction for the
Retransmission Output-1
rev
/
dir
0 : REV (REVERSE)
1 : DIR (DIRECT)
EX. If i/p is RTD.1, ZERO=0, SPAN=600,
RTR.1=4-20mA &
RT.D.1=DIR
when PV = 0, RTR o/p = 4mA
PV = 300, RTR o/p = 12mA
PV = 600, RTR o/p = 20mA
RT.D.1=REV
when PV = 0, RTR o/p = 20mA
PV = 300, RTR o/p = 12mA
PV = 600, RTR o/p = 4mA
DIR
Device
Supports
Retransmissi
on Output.