Model: LC5296-XP-DC
Doc. Ref. no.:- m61D/om/401
Issue no. 05
User’s Manual
Page 18 of 31
OPES
(
opes
)
OPEN Sensor
Status
Set Control O/P & Retransmission state
when Input OPEN condition.
down
/
up
0 : DOWN
1 : UP
UP
R.DL.1
(
r.dl.1
)
Relay Delay
(For Relay-1)
Relay Delay is amount of time (in sec), that
Relay 1 will wait before getting ON after the
ON condition occurs.
1 to 99 sec
1
HY-1
(
Hy-1
)
Hysteresis
– 1
(For Relay-1)
Hysteresis Value (in °C) for Relay-1
1 to 100
RTD Input
0.1 to 100.0
RTD.1 Input
1 to 100
Linear Input with DP=0
0.1 to 100.0
Linear Input with DP=1
0.01 to 10.00
Linear Input with DP=2
0.001 to 1.000
Linear Input with DP=3
0.1
R.DL.2
(
r.dl.2
)
Relay Delay
(For Relay-2)
Relay Delay is amount of time (in sec), that
Relay 2 will wait before getting ON after the
ON condition occurs.
1 to 99 sec
1
HY-2
(
Hy-2
)
Hysteresis
– 2
(For Relay-2)
Hysteresis Value (in °C) for Relay-2
1 to 100
RTD Input
0.1 to 100.0
RTD.1 Input
1 to 100
Linear Input with DP=0
0.1 to 100.0
Linear Input with DP=1
0.01 to 10.00
Linear Input with DP=2
0.001 to 1.000
Linear Input with DP=3
0.1
DP 1
(
dp 1
)
Decimal Point-
Input- 1
Set position of Decimal Point on Display for
PV1.
0
/
0.0
/
0.00
/
0.000
0 : 0
1 : 0.0
2 : 0.00
3 : 0.000
0
Input Type is
Linear and
Serial
DP 2
(
dp 2
)
Decimal Point-
Input- 2
Set position of Decimal Point on Display for
PV2.
0
/
0.0
/
0.00
/
0.000
0 : 0
1 : 0.0
2 : 0.00
3 : 0.000
0
Input Type is
Linear and
Serial
DI.SP
(
di.sp
)
Display Set
Point
Set which Set Point to shown in SV display
in RUN mode while device is in Auto Mode
0