  No need to feed input while calibrating Rx. o/p. just make the value in calibration 

mode equal to the displayed value. 

 
Example:

 How to change Input Type? 

 

 

 
 

7. CONTROL FUNCTION

 

  Model LC5296-XP-DC is microcontroller based ON-OFF Controller  

7.1  ON/OFF Control 

ON/OFF Controller is the simplest form of temperature control device. The output from 
the device is either on or off, with no middle state. An on-off controller will switch the 
output only when the temperature crosses the set point. For heating control, the output 
is on when the temperature is below the set point, and off above set point. 
 
Since the temperature crosses the set point to change the output stage, the process 
temperature will be cycling continually, going from below set point to above, and back 
below. In cases where this cycling occurs rapidly, and to prevent contactors and valves 
from getting damaged, an on-

off differential, or “hysteresis,” is added to the controller 

Содержание LC5296-XP-DC

Страница 1: ...OOF CONTROLLER LC5296 XP DC Masibus Automation Instrumentation Pvt Ltd B 30 GIDC Electronics Estate Sector 25 Gandhinagar 382044 Gujarat India 91 79 23287275 77 91 79 23287281 Email support masibus co...

Страница 2: ...tal Conditions 7 2 7 Special Feature 7 3 PHYSICAL SPECIFICATIONS MOUNTING DETAILS 8 3 1 External Dimensions 8 3 2 External Dimensions for dual compartment enclosure 10 4 TERMINAL CONNECTIONS 11 4 1 Si...

Страница 3: ...MODBUS RTU 24 9 1 INTRODUCTION 24 9 2 Modbus Parameter Address 25 9 3 Exceptional Response 26 10 Appendix 28 10 1 Troubleshooting 28 10 2 ON OFF LOGIC 29 10 3 Retransmission Output Table for OPEN OVER...

Страница 4: ...trademarks of Masibus Automation and Instrumentation P Ltd herein after referred to as MASIBUS Adobe Acrobat and Postscript are either registered trademarks or trademarks of Adobe Systems Incorporated...

Страница 5: ...e Conductor resistance between three wires should be equal NMRR 40 dB CMRR 120 dB Temp co 150ppm C Input Impedance 1M Voltage Input 250 Current Input Max Voltage 20VDC Use external 250ohms 0 1 for cur...

Страница 6: ...LC5296 XP DC Type Single Change over Three Terminals C NO NC Rating 2A 230VAC 30VDC Retransmission Output Number of output 2 Retransmission mapping With respect to Input no Output Signal 4 20mA 0 20m...

Страница 7: ...for 1 minute Primary terminals indicate power terminals and relay output terminals Secondary terminals indicate analog I O signal and Communication O P Insulation resistance 20M or more at 500 V DC be...

Страница 8: ...Explosion Proof EX d Area Classification Hazardous Location of Zone 1 2 Gas Groups IIA IIB IIC IP Protection IP 66 Apparatus Standard IS 2148 2004 IS 13346 2004 Material Aluminum Alloy LM 6 Finish Ant...

Страница 9: ...Model LC5296 XP DC Doc Ref no m61D om 401 Issue no 05 User s Manual Page 9 of 31 FRONT VIEW OF LC5296 XP DC INTERNAL VIEW WITH TERMINAL CONNECTION DETAILS SIDE VIEW FOR CABLE ENTRY...

Страница 10: ...s Groups IIA IIB IP Protection IP 65 As per IS IEC 60529 2001 Apparatus Standard IS IEC 60079 1 2007 Material Aluminum Alloy LM 6 Finish Anti corrosive epoxy light grey shade 631 of IS 5 Hardware High...

Страница 11: ...ntacts Use 230V 2A load ON OFF control LC5296 XP DC 7 Earth Earth Connection 8 N 9 L Power Supply Input 10 For RTD Input Only INPUT 2 Three wire Compensation 11 TC V 12 TC V For Thermocouple RTD Linea...

Страница 12: ...lace the primary and secondary power cables close to each other For thermocouple input use shielded compensating lead wires for wiring For RTD input use shielded wires that have low conductor resistan...

Страница 13: ...memory when user setting a proper data by Increment and decrement key for parameter configuration Escape Key Get to the Previous Menu level PV 1 Process Value Display PV1 4 digital 0 56 inch RED Disp...

Страница 14: ...Model LC5296 XP DC Doc Ref no m61D om 401 Issue no 05 User s Manual Page 14 of 31 6 MENU LAYOUT for LC5296 XP DC...

Страница 15: ...Model LC5296 XP DC Doc Ref no m61D om 401 Issue no 05 User s Manual Page 15 of 31 MENU LAYOUT for LC5296 XP DC...

Страница 16: ...and description Default value Shows only if Symbol Name C1 SP C1 sp Control Set Point 1 Range Depending on PV sensor type selected 100 C2 SP C2 sp Control Set Point 2 Range Depending on PV sensor type...

Страница 17: ...cally change to the Input Lower Range with changing of Input Type Refer Above Table Can be set to any value within the Input Range less the SPAN Value 199 9 If RTD 1 SPN 2 spn 2 Span 2 Automatically c...

Страница 18: ...lay Delay For Relay 2 Relay Delay is amount of time in sec that Relay 2 will wait before getting ON after the ON condition occurs 1 to 99 sec 1 HY 2 Hy 2 Hysteresis 2 For Relay 2 Hysteresis Value in C...

Страница 19: ...on RTR 1 rtr 1 Retransmissio n 1 Type Retransmission 1 Output Type This output is according to PV input Zero Span acts as Min Max value of retransmission o p scale respectively 0 5v 1 5v 0 10v 4 20 0...

Страница 20: ...ltage or Current is Jumper Selectable from the Hardware 4 20 Device Supports Dual Retransmissi on Output RT D 2 rt d 2 Retransmissio n 2 Direction Set Direction for the Retransmission Output 2 rev dir...

Страница 21: ...nput 1 PV Display Current PV CS 1 CS 1 Calibration Span 1 Calibration Span for PV Input 1 PV Display Current PV CZ 2 CZ 1 Calibration Zero 2 Calibration Zero for PV Input 2 PV Display Current PV CS 2...

Страница 22: ...e output from the device is either on or off with no middle state An on off controller will switch the output only when the temperature crosses the set point For heating control the output is on when...

Страница 23: ...onal setting 8 CALIBRATION PROCEDURE 8 1 Procedure for CAL zero and CAL span The instrument is factory calibrated for the specified range but due to long term drift of components re calibration may be...

Страница 24: ...rtZ1 retransmission 1 zero and rtS1 retransmission 1 span and if there are two retransmission outputs available then calibrate rtZ2 retransmission 2 zero and rtS2 retransmission 2 span for second retr...

Страница 25: ...ue OPEN 32767 UNDER 32765 OVER 32766 Sr No Parameters Absolute Address Type Access Type 1 Input Type 1 40001 Int R W 2 Zero 1 40002 Int R W 3 Span 1 40003 Int R W 4 Filter 40004 Int R W 5 SET Type 1 4...

Страница 26: ...d It must be 01 05 03 or 06 The function code received in the query is not allowable action for the slave 02 Illegal address value The data address received in the query is not an allowable address fo...

Страница 27: ...Page 27 of 31 3 Refer Menu Mode Description Table the value Range of each Parameter EX Input Type Applicable Range 7 to 12 Input Type 1 Input Type 2 Value RTD 0 1 degree RTD 0 1 degree 7 RTD 1 degree...

Страница 28: ...x 10 1 Troubleshooting If the operating display does not appear after turning on the controller s power follow the measures in the procedure below If a problem appears complicated contact our sales re...

Страница 29: ...Up scale Off Off Down scale On On 10 3 Retransmission Output Table for OPEN OVER UNDER condition RETRASMISSION VARIABLE SCALE ACTION OPEN OVER UNDER 4 20mA PV UP DIR 20 8 20 8 3 2 PV DOWN REV 3 2 3 2...

Страница 30: ...ess value 1 1 IN 2 Relay 1 for Process value 2 RL 2 0 IN 1 Relay 2 for Process value 1 1 IN 2 Relay 2 for Process value 2 Retransmission RT 1 0 IN 1 Retransmission 1 for Process value 1 1 IN 2 Retrans...

Страница 31: ...mper Setting for Retransmission card m61Cao102 10 7 Load connection Electrical precautions during use Electrical noise generated by switching of inductive loads can create momentary disruption erratic...

Отзывы: