Mantracourt Electronics Limited
T24 Technical Manual
47
between receiving Data Provider packets from the
paired device will cause the display to show ------.
Default = 3
( range:0 to 65535 default:3 )
KeepAwakeInt
66
Set or read the interval in seconds between the
handheld transmitting StayAwake signals to the paired
device.
( range:0 to 65535 default:5 )
UINT16
RW
DisplayUpdate
74
Set or read the interval between LCD updates. Default
= 300
UINT16
RW
PairWait
67
Set or read the period in seconds that the handheld
will wait for another device to pair when placed into
pair mode.
( range:0 to 65535 default:5 )
UINT8
RW
Format
70
Set or read the format for the display. Here you can
define how the value will be displayed and where the
decimal point will appear. By including a non zero
value this will define the resolution of the displayed
value. i.e. the smallest step size of value changes.
Default = 0000.001
STRING 8
bytes
RW
ZeroSupp
71
Set or read whether to show the value on the display
with zero suppression.
0 = No zero suppression
1 = Zero suppression
UINT8
RW
ZeroBand
72
Set or read the band within which zero will be
displayed. As soon as the value exceeds ±ZeroBand the
actual value will be displayed. This will effectively
mask small changes after taring the device.
FLOAT
RW
Overload
73
Set or read the value of the display above which
instead of the value being displayed 'Overload' will be
displayed.
FLOAT
RW
ScaleInLo
75
Set or read a low input value at which you know what
display you require. Default = 0
FLOAT
RW
ScaleInHi
77
Set or read a high input value at which you know what
display you require. Default = 1
FLOAT
RW
ScaleDisplayLo
76
Set or read a low display value for the input value
stated in ScaleInLo. Default = 0
FLOAT
RW
ScaleDisplayHi
78
Set or read a high display value for the input value
stated in ScaleInHi. Default = 1
FLOAT
RW
BinaryStart
79
Set or read the starting byte (starting from zero) from
data carried in a binary data provider at which to
extract the single displayed value. Defaults to zero.
NOTE: This is only required for modules that transmit
binary data provider data and the default is set to
display data from a T24-SAF
UINT8
RW
BinaryDataType
80
Set or read the data type of the data to extract from
the binary data provider. Defaults to 3=INT32
0=Disabled
1=UINT8
2=UINT16
3=INT32
4=FLOAT
UINT8
RW
Reset
54
Restarts the device and utilises new channel and
encryption keys if those have been changed and saved.
Command
Save
55
Save any changes made to parameters. Required
before power cycling or issuing a Reset command.
Requires 500mS recovery time after executing.
Command
NOTE: All changes require a SAVE command to enable them to survive through power cycle or RESET command.
Power Supply
Recommend using alkaline AA cells as rechargeable are too low voltage and lithium may not be able to supply the
current for the radio to start up.