Mantracourt Electronics Limited
T24 Technical Manual
61
can include text or tokens.
bytes
Line20
88
Read or set the data for line 20 of the serial output. You
can include text or tokens.
STRING 32
bytes
RW
ExtZero
68
Read the value derived from another device when
ExtZeroDataTag
is set. (The system zero is a value
contained in the data from an external device)
FLOAT
R
ExtZeroDataTag
119
Set or read the 2 byte Data Tag of the Data Provider
Packet that will supply a system zero value. This value will
be subtracted from the gross or net summed values. This
allows the same T24-SO assembly to be used with different
sets of data providers each supplying its own system zero
value.
UINT16
RW
PrintDataTag
128
Set or read the 2 byte Data Tag of the Data Provider
Packet that will trigger a 'print'.
The value contained in this packet can be referenced using
the
<F1>
token.
UINT16
RW
LineDelay
130
Reads or sets the number of milliseconds between each
line being sent out. This is useful to control the rate that a
page is sent to a printer for example.
UINT16
RW
MinInterval
131
Set or read the sets the minimum interval between 'Prints'. UINT16
RW
LogNumber
132
Set or read the log number that will be used next time a
'Print' output is generated.
FLOAT
RW
LogDigits
133
Set or read the number of digits to display the log number
as.
UINT8
RW
NVLog
149
Set or read whether to store the log number between
power cycles. As this writes to flash each time the <LOG>
token is referenced it is recommended that this is set to
zero (Off) if the log number is referenced at a rate greater
then every 30 seconds.
UINT8
RW
Duplicate
134
Set or read whether to generate two 'Print' outputs for
every trigger. This can be used with printers that do not
have carbon copy capability.
UINT8
RW
SwitchMode
135
Set or read the action to take when the switch input is
activated.
Value
Description
0
Perform 'Print'.
1
Toggle between gross mode and net
mode. When entering net mode all inputs
will be tared.
UINT8
RW
NetMode
136
Set or read the mode of operation. Set to true to tare the
inputs and enter net mode. Set to zero to remove tares
and enter gross mode.
Value
Description
0
Remove tares and enter gross mode.
1
Tare the inputs and enter net mode
UINT8
RW
Gross
145
Read the gross sum of all active inputs. Equivalent of value
generated for <GRO> token.
FLOAT
R
Net
146
Read the net sum of all active inputs. Equivalent of value
generated for <NET> token.
FLOAT
R
GrossText
137
Read the set the text used to replace the <GN> token when
in gross mode.
STRING 10
bytes
RW
NetText
138
Read the set the text used to replace the <GN> token when
in net mode.
STRING 10
bytes
RW
PrintOnError
139
Read the set whether to trigger a 'Print' output when an
error first occurs on any of the inputs.
UINT8
RW