Mantracourt Electronics Limited
T24 Technical Manual
67
power cycling or issuing a Reset command.
Requires 500mS recovery time after executing.
SelectedRange
60
Returns the currently selected output range.
Value
Description
0
0V to +5V
1
-5V to +5V
2
0V to +10V
3
-10V to +10V
4
0 to 20mA (sink)
5
4 to 20mA (sink)
6
0 to 20mA (source)
7
4 to 20mA (source)
UINT8
R
ErrorState
61
Read the current error state. Each bit value represents a
different state.
Bit
Value
Description
1
Timeout
2
Remote Error
4
Remote Battery
8
Scaling Error
UINT8
R
Value
62
Read the current input value.
FLOAT
R
InMin
100
The input value at which the output will be at 0%.
FLOAT
RW
InMax
101
The input value at which the output will be at 100%.
FLOAT
RW
Timeout
102
The time allowed between data arrivals greater than which
will trigger the TimeOutAction.
INT32
RW
TimeoutAction
103
Select the action to trigger when data does not arrive for
the Timeout period.
Value
Description
0
None
1
Minimum Full Scale
2
Maximum Full Scale
3
Minimum Output
4
Maximum Output
5
Half Full Scale
6
Hold Last Output
UINT8
RW
RemoteErrAction
104
Select the action to trigger when the remote device
reports an error.
Value
Description
0
None
1
Minimum Full Scale
2
Maximum Full Scale
3
Minimum Output
4
Maximum Output
5
Half Full Scale
6
Hold Last Output
UINT8
RW