INSTALLING THE GLYCOL CIRCULATING PUMP
AND MOTOR KIT
1. Remove the lid from the Beermaster refrigeration
unit.
2. Install the glycol circulating motor with pump to
the motor shelf located in the Beermaster Glycol
Unit motor compartment (see “Motor Installation”
figure).
NOTE: Motor must be installed with the glycol pump
facing away from the glycol bath.
3. Locate the pickup tube and discharge tube
assemblies. Slide one piece of insulation over
each of the tube assemblies (see “Tube
Installation” figure).
4. Attach the pickup tube to the inlet side of the
glycol pump making sure the opposite end from
the pump is submerged in glycol bath.
5. Attach the discharge tube to the outlet side of the
glycol pump.
6. Slide the 1/2" x 1/2" John Guest Elbow, supplied
in kit, onto the end of the discharge tube at pump
motor assembly.
7. Locate the circulator pump discharge cooling
tube, supplied with kit, and insert into the water
bath area. Insert straight end of tube into the John
Guest elbow fitting as shown.
8. Insert the two 1/2" O.D. John Guest bulkhead
unions, supplied in kit, into the pre-punched holes
located in the end of the refrigeration unit.
9. Locate the two 1/2" O.D. tube retaining collets,
provided in kit, and insert into each of the John
Guest bulkhead unions.
10. Insert the free end (bent end) of the circulator
pump coil tube into the lower John Guest
bulkhead union.
NOTE: Do Not discard the condensation cover over
the reservoir tank. It is necessary to prevent excessive
condensation from diluting the water-glycol mixture.