4. The trap(s) must be of minimum height of 3"
(7.6 cm) and a width of 6" (15.2 cm) to minimize
oil accumulation. The traps can also be bent out
of the refrigeration tubing. Carefully bend the
tubing down 12", and then sweep the tubing back
up.
5. It is critical that the Multiplex remote condensing
line size specifications for the specific model be
maintained. The specifications are 1/2" discharge
and 3/8" liquid lines.
INSTALLING THE MULTIPLEX REMOTE
CONDENSER
The Multiplex remote condensing units have a
208-230 Volt, 50/60 HZ, 1 PH fan motor that includes a
permanent split capacitor and internal overload
protection. The electrical wires from the refrigeration
unit wire to the condenser. The electrical installation
must be in accordance with local codes, National
Electrical Code and regulations.
1. Determine a position for installation that will allow
access for maintenance and is free from
obstruction. Verify hot air discharge from other
condensers does not interfere with the inlet of this
condenser.
2. Install the four legs to the sides of the condenser
using the mounting bolts provided.
To the
Condenser
Discharge Line Trap Every
25 Vertical ft. (7.62 m)
3 ft (.9 m) (minimum) of Discharge
Line Trap at the Compressor
Compressor
3" (7.6 cm) x 6" (15.2 cm)
Maximum Trap Area
Discharge Line
Condenser Trap