EVAPORATOR THERMOSTAT
Function
Mechanical Timer - Energizes the timer motor when
the evaporator temperature drops below the control
set point.
SCR Timer - Supplies and removes power to SCR
trigger.
No Timer - Initiates and terminates freeze and harvest
cycles.
Operation
Thermostat contacts C & L are closed at temperatures
above cut in and contacts C & H are closed at
temperatures below cut in.
Setting Control For Proper Operation
Correct setting will vary with operating ambient. To
obtain correct setpoint, capture and weigh the ice from
1 freeze cycle (refer to ice production check for
complete details).
Refer to Cycle Time/24 hour Ice Production charts for
correct cube weight and quantity. White or misshapen
cubes indicate cleaning is required.