Part Number 80-1479-3 10/10
61
DISCHARGE LINE TEMPERATURE ABOVE 71°C AT
END OF FREEZE CYCLE:
Ice machines that are operating normally will have
consistent maximum discharge line temperatures
above 71°C.
DISCHARGE LINE TEMPERATURE BELOW 71°C AT
END OF FREEZE CYCLE:
Ice machines that have a flooding expansion valve will
have a maximum discharge line temperature that
decreases each cycle.
Verify the expansion valve sensing bulb is 100%
insulated and sealed airtight. Condenser air contacting
an incorrectly insulated sensing bulb will cause
overfeeding of the expansion valve.
Verify the expansion valve sensing bulb is positioned
and secured correctly.