HEADMASTER CONTROL VALVE FAILURE LIST
CVD1476
Freeze Cycle
Valve not maintaining discharge pressure.
The water regulating valve maintains the freeze
cycle discharge pressure.
Discharge pressure extremely high; Liquid line
entering receiver feels hot.
Verify water regulating valve is set and/or operating
correctly.
Headmaster valve is stuck in bypass.
Discharge pressure low, Liquid line entering
receiver feels warm to hot.
Ice Machine low on charge. Refer to “Low on
Charge Verification.”
Harvest Cycle
Discharge pressure normal or high, Liquid line
entering receiver feels warm, suction pressure is
low.
Headmaster valve not bypassing. Refer to “Harvest
Cycle Headmaster Control Valve Failure List” for
diagnostic procedure.