Part Number STH025 8/12
139
One Evaporator, Two TXV 30” Models
Tubing routing for one evaporator with two TXV’s is
different. The evaporator has two inlets and outlets. Fill
pattern varies depending on which circuit is affected,
Extremely Thin at the Evaporator Outlet
will first be
visible either 1/4 or 3/4 of the way down the
evaporator.
Extremely Thin at the Evaporator Inlet
will show at
the bottom of the evaporator or 1/2 of the way down
depending on the circuit affected.
ICE
Thin at Inlet
Inlet
Outlet
ICE
ICE
ICE
ICE
Inlet
Outlet
Thin at Outlet
Содержание b970 series
Страница 2: ......
Страница 28: ...28 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 58: ...58 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 210: ...210 Part Number STH025 8 12 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Страница 250: ...250 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 252: ...252 Part Number STH025 8 12 I0300 I0450 I0500 I0520 Self Contained Air Water cooled 1 Ph ...
Страница 253: ...Part Number STH025 8 12 253 I0320 Self Contained Air Water cooled 1 Ph ...
Страница 254: ...254 Part Number STH025 8 12 I0500 Remote Air cooled 1Ph ...
Страница 255: ...Part Number STH025 8 12 255 I0600 I0850 I1000 I1200 Self Contained Air Water cooled 1 3 Ph ...
Страница 256: ...256 Part Number STH025 8 12 I0600 I0850 I1000 Remote Condenser Air cooled 1 3 Ph ...
Страница 257: ...Part Number STH025 8 12 257 I1400 I1800 Self Contained Air Water cooled 1 3 Ph ...
Страница 258: ...258 Part Number STH025 8 12 I1400 I1800 Remote Air cooled 1 3 Ph ...
Страница 262: ...262 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 263: ......