SYMPTOM #2 - LOW PRODUCTION, LONG
FREEZE CYCLE
Ice Machine has a Long Freeze Cycle.
Ice Formation is Thick
or
Thin on Inlet or Outlet of Evaporator
or
Low Production
How to Use the Freeze Cycle Refrigeration System
Operational Analysis Table
GENERAL
These tables must be used with charts, checklists and
other references to eliminate refrigeration components
not listed on the tables and external items and
problems which can cause good refrigeration
components to appear defective.
The tables list five different defects that may affect the
ice machine’s operation.
NOTE:
A low-on-charge ice machine and a starving
expansion valve have very similar characteristics and
are listed under the same column.
NOTE:
Before starting, see “Before Beginning
Service” for a few questions to ask when talking to the
ice machine owner.
Содержание b970 series
Страница 2: ......
Страница 28: ...28 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 58: ...58 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 210: ...210 Part Number STH025 8 12 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Страница 250: ...250 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 252: ...252 Part Number STH025 8 12 I0300 I0450 I0500 I0520 Self Contained Air Water cooled 1 Ph ...
Страница 253: ...Part Number STH025 8 12 253 I0320 Self Contained Air Water cooled 1 Ph ...
Страница 254: ...254 Part Number STH025 8 12 I0500 Remote Air cooled 1Ph ...
Страница 255: ...Part Number STH025 8 12 255 I0600 I0850 I1000 I1200 Self Contained Air Water cooled 1 3 Ph ...
Страница 256: ...256 Part Number STH025 8 12 I0600 I0850 I1000 Remote Condenser Air cooled 1 3 Ph ...
Страница 257: ...Part Number STH025 8 12 257 I1400 I1800 Self Contained Air Water cooled 1 3 Ph ...
Страница 258: ...258 Part Number STH025 8 12 I1400 I1800 Remote Air cooled 1 3 Ph ...
Страница 262: ...262 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 263: ......