Part N
umber ST
H025 8/12
93
E21
T1 Fault
T1 Sensor
Each thermistor reading is monitored continuously using six second average values. During Pre-chill
a thermistor had a six second average thermistor values fall outside of the valid temperature range.
E22
T2 Fault
T2 Sensor
E23
T3 Fault
T3 Sensor
E24
T4 Fault
T4 Sensor
E25
Bin Prb Fault
Bin Low Sens
Each thermistor reading is monitored continuously using six second average values. A
thermistor had a six second average value outside of the valid range for more than 10 continous
minutes
E26
Bin Prb Fault
Bin Med Sens
E27
Bin Prb Fault
Bin Hi Sens
E28
AUCS
AUCS (Aucs not Present) (Event
Log only - No alarm)
When the AUCS clean option is selected from the menu, the control checks for the presence of the
AUCS board and if the AUCS is not connected it will signal an Event “AUCS”. This will be cleared
as soon as the hardware is detected.
E29
USB COMM
USB Comm (Event Log only - No
Alarm)
USB Communication error, no USB drive in port or defective USB drive
E30
USB DNLD
USB download error (dlnd) Event
Log only - No alarm)
USB Download error related to USB drive or a defective USB drive
E31
Safe Mode
Safe Mode (Event Log only - No
alarm)
Safe mode allows the ice machine to operate for a period of time in the event of a WLP or ITP
sensor failure. The controller allows the machine to operate based on historical information
collected and model data information stored in the controllers memory.
E-Log Display Text
Error Description
Definition
Detail Event Log Service Definition
Содержание b970 series
Страница 2: ......
Страница 28: ...28 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 58: ...58 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 210: ...210 Part Number STH025 8 12 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Страница 250: ...250 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 252: ...252 Part Number STH025 8 12 I0300 I0450 I0500 I0520 Self Contained Air Water cooled 1 Ph ...
Страница 253: ...Part Number STH025 8 12 253 I0320 Self Contained Air Water cooled 1 Ph ...
Страница 254: ...254 Part Number STH025 8 12 I0500 Remote Air cooled 1Ph ...
Страница 255: ...Part Number STH025 8 12 255 I0600 I0850 I1000 I1200 Self Contained Air Water cooled 1 3 Ph ...
Страница 256: ...256 Part Number STH025 8 12 I0600 I0850 I1000 Remote Condenser Air cooled 1 3 Ph ...
Страница 257: ...Part Number STH025 8 12 257 I1400 I1800 Self Contained Air Water cooled 1 3 Ph ...
Страница 258: ...258 Part Number STH025 8 12 I1400 I1800 Remote Air cooled 1 3 Ph ...
Страница 262: ...262 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 263: ......