180
Part Number STH025 8/12
5. Ohm Ice Thickness Probe
NOTE: Verify meter leads are properly connected to
VOM with the red meter lead connected to positive &
the black meter lead connected to negative
•
Disconnect Ice Thickness Probe from control
board
•
Connect red meter lead to the red wire and the
black meter lead to the black wire - Normal
readings = 1.4 to 2.5 K
Ω
's.
•
Reverse leads - Connect black meter lead to the
red wire, red meter lead to the black wire - Normal
readings = 1.2 to 1.5 K
Ω
's.
6. Check control board voltage
•
Set VOM to DC voltage scale - Check voltage
across the top and bottom pin - Normal readings =
3.25 to 3.35 VDC.
Pass
Ohm values are within range - Check control board
voltage at the ice thickness probe connection.
Fail
Replace ice thickness probe.
Pass
Control board voltage is normal
Fail
Replace control board
Содержание b970 series
Страница 2: ......
Страница 28: ...28 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 58: ...58 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 210: ...210 Part Number STH025 8 12 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Страница 250: ...250 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 252: ...252 Part Number STH025 8 12 I0300 I0450 I0500 I0520 Self Contained Air Water cooled 1 Ph ...
Страница 253: ...Part Number STH025 8 12 253 I0320 Self Contained Air Water cooled 1 Ph ...
Страница 254: ...254 Part Number STH025 8 12 I0500 Remote Air cooled 1Ph ...
Страница 255: ...Part Number STH025 8 12 255 I0600 I0850 I1000 I1200 Self Contained Air Water cooled 1 3 Ph ...
Страница 256: ...256 Part Number STH025 8 12 I0600 I0850 I1000 Remote Condenser Air cooled 1 3 Ph ...
Страница 257: ...Part Number STH025 8 12 257 I1400 I1800 Self Contained Air Water cooled 1 3 Ph ...
Страница 258: ...258 Part Number STH025 8 12 I1400 I1800 Remote Air cooled 1 3 Ph ...
Страница 262: ...262 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 263: ......