HARVEST ASSIST AIR PUMP
FUNCTION
The air pump helps break the vacuum between the
sheet of ice and the evaporator which results in shorter
harvest cycles.
SPECIFICATIONS
115 Volt or 230 Volt - matches the ice machine
voltage.
CHECK PROCEDURE
1. The air pump is wired in parallel with the harvest
valve - Verify the ice machine is in the harvest
cycle and the harvest valve is energized.
2. If there is voltage at the air pump connector, use a
volt ohm meter to verify there is no continuity
through the motor windings then replace motor.
Содержание b970 series
Страница 2: ......
Страница 28: ...28 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 58: ...58 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 210: ...210 Part Number STH025 8 12 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Страница 250: ...250 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 252: ...252 Part Number STH025 8 12 I0300 I0450 I0500 I0520 Self Contained Air Water cooled 1 Ph ...
Страница 253: ...Part Number STH025 8 12 253 I0320 Self Contained Air Water cooled 1 Ph ...
Страница 254: ...254 Part Number STH025 8 12 I0500 Remote Air cooled 1Ph ...
Страница 255: ...Part Number STH025 8 12 255 I0600 I0850 I1000 I1200 Self Contained Air Water cooled 1 3 Ph ...
Страница 256: ...256 Part Number STH025 8 12 I0600 I0850 I1000 Remote Condenser Air cooled 1 3 Ph ...
Страница 257: ...Part Number STH025 8 12 257 I1400 I1800 Self Contained Air Water cooled 1 3 Ph ...
Страница 258: ...258 Part Number STH025 8 12 I1400 I1800 Remote Air cooled 1 3 Ph ...
Страница 262: ...262 Part Number STH025 8 12 This Page Intentionally Left Blank ...
Страница 263: ......