Screws has to be fixed in wall/ceiling construction.
(If it is needed use steel bracket).
Position:
1
Damper with installation frame E6
2
Cement lime plates min. thickness 40 mm
(min. density 450 kg/m³)
3
Cement lime prisms min. thickness 40 mm
(min. density 450 kg/m³)
All parts are glued with glue Promat K84 and
secured by screws.
Dampers has to be suspended in an
appropriate manner see chapter 9.
Screw
(min. 4x80)
*
Installation frame E6 is suitable for:
●
Installation outside solid wall/ceiling construction with cement lime plates
On the inside is installation frame equipped by intumescent sealing. It enlarges its capacity and air
proofs the gap between installation frame and damper body.
●
Installation frame:
cement lime plates
●
Fasteners:
galvanized plate
●
a x b = (A + 105
+3
mm) x (B + 105
+3
mm)
* min. 110 - Concrete/ min. 125 - Aerated concrete