75
Position:
1
Fire damper
2
Damping pad
3
Extension piece
4
Threaded rod
5
Mounting rail
6
Nut
7
U - Washer
8
Washer
9
Screw connection
10 Mounting profile
11 Mounting bracket
12 Fire-resistant board
Examples of using materials:
The damper must not be suspended or anchored. The duct must be anchored after national rules,
like in fig. 84 - as an example. It can be suspended by using threaded rods and a mounting
profiles.
Load the suspension system depend on weight of the fire damper.
Damper can be suspended from the ceiling construction or supported above the ceiling construction.
Damper assembly procedures must be done so as all load transfer from the fire separating
constructions to the damper body is absolutely excluded. Back-to-back air-conditioning piping
must be hung or supported so as all load transfer from the back-to-back piping to the damper is
absolutely excluded.
Threaded rods longer than 1,5 m require fire-resistant insulation.
Threaded rod fixing to the ceiling construction - see fig. 81