background image

Page 1 of 11 pages 

Health and Safety 

1.1 

Only competent personnel may carry out the work outlined within this document. 

1.2 

The  wearing  of  appropriate  Personal  Protective  Equipment  (gloves,  footwear, 
safety glasses etc.) is required for safe working and as the site dictates.  
Dampers may be heavy. Large dampers will require suitable lifting and 
supporting equipment, with due consideration given for manual handling. 

1.

4

Dampers  may  close  without  warning.  Do  not  introduce  limbs/fingers  between 
blades whilst the actuator is fitted. 

1.5 

Where  dampers  are  only  accessible  with  the  need  for  additional  elevation,  any 
equipment used should be done so with due consideration to the Work at Height 
regulations 2005 and current site rules.  

1.6 

All work should be carried out in accordance with HSE guidelines and regulations 
and any specific local site rules. 

Important 

2.1 

These  instructions should be read  in  its  entirety  before commencing  work.  The 
installer  must  be  Competent  with  the  manufacturer’s  separating  element 
construction. 

2.2 

Actuators are IP54 rated 

– Check actuator connection box is suitably located. 

2.3 

Do not cut/shorten the Thermal Fuse lead (-TF Actuators).  This will render the 
unit inoperable and invalidate the warranty. 

2.4 

Where an actuator is supplied with a Thermal Fuse (TF), the TF MUST be fitted 
in accordance with instructions.  Failure to meet this requirement will invalidate 
the warranty and the damper will fail to respond as designed/tested. 

2.5 

All Fire / Smoke Damper installations must be carried out to the satisfaction of the 
appropriate Building Control officer and/or specifying authority. 

2.6 

Refer to actuator label for wiring of actuator. 

2.7 

Refer to section 20 for testing. Complete Insp Check List (at end of this document) 

2.8 

For  existing  dry  walls 

–  When  cutting  the  opening  for  damper,  and  (partial) 

removal of stud is unavoidable, ensure the structure is sufficiently supported to 
conform to design specification 

2.9 

Dry wall openings must be lined.  

2.10 

Ensure  that  appro

priate  ‘fire-rated’  plasterboard  is  used  throughout  the 

construction of drywall partitions that need to act as fire-barriers. 

2.11 

Ductwork to be fitted and connected in accordance with DW 144/145. Aluminium 
rivets should be used (to act as breakaway joint). 

2.12 

All  installations  are  subject  to  local  Building  Control  Approval  (BCA).  Tested 
Installations are detailed herein. If the proposed installation has minor variations 
to  that  shown,  acceptance  from  BCA  should  be  sought  before  proceeding. 
Manufacturers are not able to ‘approve’ specific installation methods 

2.13 

Where  more  than  one  duct  penetrates  a  wall  or  floor,  adjacent  fire  damper 
assemblies should be separated by a structural element with a minimum width of 
200mm (to comply with BS EN1366-2 13.6). 

Equipment required 

3.1 

Equipment and tools will vary dependent upon the fire barrier construction that the 
damper is being installed within. Standard equipment  that are normally used for 
the building of the particular barrier should suffice. 

3.2 

Access-equipment as necessary. 

3.3 

Temporary support equipment (to retain damper in position). 

3.4 

Cordless drill with 2,5mm and 10mm drill bits for fitting TF. 

3.5 

Phillips 

№2 screwdriver to suit thermal fuse screws 

3.6 

Screwdriver to suit junction box terminals. 

FSD-TD Damper 
Installation, Operating and Maintenance Instructions 

1.

3

Содержание FSD-TD Damper

Страница 1: ...ding Control officer and or specifying authority 2 6 Refer to actuator label for wiring of actuator 2 7 Refer to section 20 for testing Complete Insp Check List at end of this document 2 8 For existing dry walls When cutting the opening for damper and partial removal of stud is unavoidable ensure the structure is sufficiently supported to conform to design specification 2 9 Dry wall openings must ...

Страница 2: ...e for TD drive box 5 3 2 Cut size nominal damper width 121mm 2 x wall board thickness by nominal damper height 96mm 2 x wall board thickness 5 3 3 Example for 500x300 damper and 12 5mm wall board cut hole should be 646mm x 421mm 500 121 2x12 5 x 300 96 2x12 5 5 4 Mark out the position and size of required cut size on the wall 5 5 Using appropriate means e g jig saw cut the hole in the wall removin...

Страница 3: ...he wall Make the hole in the wall Wall only Prepare a pair of spacing blocks approx 10mm high x 25mm square from any available material such as drywall boards Position spacing blocks within the opening at extremities of damper and stand the damper with blades running horizontally on blocks so that damper is central in opening Fix the angle frame to the wall using suitable expansion bolt steel slee...

Страница 4: ...he opening in corresponding positions to the HEVAC frame builder s ties 8 5 Bend the builder s ties out See Fig 5 8 6 Vertical installation only Prepare a pair of spacing blocks approx 25mm cubed from any available material such as drywall boards Position spacing blocks within the opening at extremities of damper and stand the damper on blocks so that damper is central in opening 8 7 While support...

Страница 5: ... sides overlap and affix 150mm wide strips of firebatt to form a pattress around the damper Fig 8 Drop rod load bearing specification Drop rod size Max load per pair of studs kg E60 E120 E240 M6 54 7 36 5 21 9 M8 100 4 66 9 40 2 M10 159 8 106 6 63 9 M12 233 1 155 4 93 2 10 Sleeve and Angle Installation Procedure Fig 10 10 1 This installation method is suitable for all wall structures the installat...

Страница 6: ...eparation instructions 11 2 This installation method is to be followed when extra support is required due to the damper size weight or other factors 11 3 Ensure that the supporting drop rods are suitably sized for the damper Refer Fig 8 11 4 Ensure that the drop rods are anchored fastened in the top supporting structure 11 5 Depending on wall thickness it may ease connection of ductwork if connect...

Страница 7: ...amper centrally in wall opening 12 5 Prepare 16 off pattress pieces from plasterboard of same material as main construction Plasterboard pattress should be sufficiently wide to butt up to damper spigots duct and overlap the outer edge of the track lining the opening by at least 10mm They need to be long enough to form neat corners 12 6 Two layers of pattress are required each side of wall and the ...

Страница 8: ...ring drive directions 16 3 Manually wind the actuator using the crank handle provided fully to the reset position and lock into position Due care should be taken to stop winding when slight resistance is encountered over winding can result in permanent damage to the damper actuator which may invalidate the warranty 16 4 Damper must be in closed position 16 5 Fit actuator cradle in desired orientat...

Страница 9: ...E END in 60 seconds Confirm visually that blade position and indication pointer on the actuator corresponds 20 11 If the damper has seized failing to reach either drive end or spring end 20 11 1 Isolate and remove actuator Refer to section 19 20 11 2 Spray a light lubricant into blade end bearings through the holes on the side gaskets 20 11 3 Using the 12mm A F spanner on the TD box Drive Shaft be...

Страница 10: ...ly appointed competent person 23 4 The installation needs to be inspected thoroughly before the damper actuation is tested 23 5 Actuation testing should be completed as follows 23 5 1 Isolate the power 23 5 2 Remove access door s 23 5 3 Test manually using the crank handle provided to set the damper to the normal state powered state A quarter turn in the opposite direction locks it Visually confir...

Страница 11: ...TTED BY Print name Signature Company Date FAIL SAFE POSITION POWER OFF position Tick appropriate box OPEN SHUT FINAL INSPECTION BY Print name Signature Company Date This document is available for free download from the BSB website This document is subject to change without notice BSB Engineering Services Ltd Tel 44 0 1795 422609 Email enquiries bsb dampers co uk website www bsb dampers co uk Dec 2...