background image

Page 9 of 11 pages 

 
 

20  Routine Inspection, Testing and Maintenance  

20.1 

In accordance with BS 9999 Annex W.1, inspection should be undertake annually. 
Local  regulations/conditions  may  override  this  with  periodic  Inspection  being 
carried  out  more  frequently  where  corrosive  or  dirty  conditions  prevail.  The 
maintenance  log  should  be  reviewed  at  each  inspection  and  the  frequency 
adjusted as required dependent upon findings. (BSB recommend a maximum of 
1  year  between  inspections  and  to  start  more  frequently  initially,  and  reduce 
frequencies only if conditions are proven to allow). 

20.2 

For actuators fitted with a thermal fuse), check TF is correctly fitted to duct (Refer 
to section 14) 

20.3 

Where a thermal fuse is present, the LED on the thermal fuse will be illuminated 
when the actuator is powered.  Refer to Section 21.1, if it is not illuminated. 

20.4 

Remove access door to reveal damper’s internal elements. 

20.5 

Visually inspect the internal damper elements for signs of corrosion, obstruction 
or accumulated dirt/dust. 

20.6 

If there are any obstructions or if the damper

’s blades/gasket seals are dirty, they 

need to be cleaned.  It is recommended to remove the actuator before cleaning 
the internal elements to avoid trapping your fingers. (Refer to section 19) 

20.7 

Visually  check  that  the 

damper  is  in  its  ‘powered  state’  (opposite  to  fail-safe 

position).  If the 

damper is not in its ‘powered state’, refer to fault finding chart, 

otherwise continue.  

20.8 

Temporarily  remove  electrical  power  to  the  actuator  (either  by  using  the  toggle 
switch on the thermal fuse (TF actuator), or by isolating power to actuators without 
a thermal fuse) 

20.9 

The actuator should reach its SPRING-END (fail-safe position) in <30 seconds.  
Confirm  visually  that  the  blade  position  and  indication  pointer  on  the  actuator 
corresponds. 

20.10  Release  the  TF  toggle  (TF)  or  Turn  power  back  on  to  the  actuator  (NTF)and 

ensure  it  reaches  its  DRIVE  END  in  <60  seconds.    Confirm  visually  that  blade 
position and indication pointer on the actuator corresponds. 

20.11  If the damper has seized (failing to reach either drive end or spring end):- 

20.11.1  Isolate and remove actuator. (Refer to section 19) 
20.11.2  Spray a light lubricant into blade end bearings through the holes 

on the side gaskets. 

20.11.3  Using the 12mm A/F spanner on the TD box Drive Shaft, begin to 

progressively operate the blades manually.  

20.11.4  Open  the  damper  using  a  12mm  A/F  spanner  on  the  TD  box.  

Check for foreign items in and around blades, paying particular 
attention to blade fishtails.  Remove any obstructions. 

20.11.5 

Clean  the  inside  of  the  damper  case  where  the  blades  make  contact  with  the 
gasket seals. Use a soft cloth with a light application of light lubricant. (Connect 
Duck Oil recommended) 

20.11.6 

Lightly apply a light lubricant into blade axle bearings depressing the side gaskets 
to allow access. It may be necessary to re-apply lubricant a couple of times, whilst 
operating the damper using the 12mm A/F spanner, until the torque has reduced 
to less than 5Nm for mid-range travel, and 10Nm for full damper closure. 

           20.11.17   There should be no more than a thin film of lubricant applied. Remove all excess    
                            lubricant. It is particularly important as excess oil will tend to collect dirt and dust     
                            which will have a negative effect on dampers remaining clean. 

20.11.7 

Refit the actuator (Refer to sections 15 or 16). 

20.11.8 

Switch on power to the actuator. 

20.11.9 

The actuator should reach its ‘powered state’ position in <60 seconds. If it does 
not, refer to section 21. 

20.11.10 

Replace access doors, and ensure the damper is left in its ‘powered state’. 

20.11.11  Record all work that has been undertaken in the maintenance log. 

  20.11.12   It is important to log and review maintenance frequency based on  
                   inspections and test history. 

20.11.13  It is important to log and review maintenance frequency based on inspections and 

test history. 
The use of heavy oil is not recommended, as this can lead to a build-up of dust/dirt 
on damper surfaces. 

20.11.14  The actuator is maintenance-free. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Содержание FSD-TD Damper

Страница 1: ...ding Control officer and or specifying authority 2 6 Refer to actuator label for wiring of actuator 2 7 Refer to section 20 for testing Complete Insp Check List at end of this document 2 8 For existing dry walls When cutting the opening for damper and partial removal of stud is unavoidable ensure the structure is sufficiently supported to conform to design specification 2 9 Dry wall openings must ...

Страница 2: ...e for TD drive box 5 3 2 Cut size nominal damper width 121mm 2 x wall board thickness by nominal damper height 96mm 2 x wall board thickness 5 3 3 Example for 500x300 damper and 12 5mm wall board cut hole should be 646mm x 421mm 500 121 2x12 5 x 300 96 2x12 5 5 4 Mark out the position and size of required cut size on the wall 5 5 Using appropriate means e g jig saw cut the hole in the wall removin...

Страница 3: ...he wall Make the hole in the wall Wall only Prepare a pair of spacing blocks approx 10mm high x 25mm square from any available material such as drywall boards Position spacing blocks within the opening at extremities of damper and stand the damper with blades running horizontally on blocks so that damper is central in opening Fix the angle frame to the wall using suitable expansion bolt steel slee...

Страница 4: ...he opening in corresponding positions to the HEVAC frame builder s ties 8 5 Bend the builder s ties out See Fig 5 8 6 Vertical installation only Prepare a pair of spacing blocks approx 25mm cubed from any available material such as drywall boards Position spacing blocks within the opening at extremities of damper and stand the damper on blocks so that damper is central in opening 8 7 While support...

Страница 5: ... sides overlap and affix 150mm wide strips of firebatt to form a pattress around the damper Fig 8 Drop rod load bearing specification Drop rod size Max load per pair of studs kg E60 E120 E240 M6 54 7 36 5 21 9 M8 100 4 66 9 40 2 M10 159 8 106 6 63 9 M12 233 1 155 4 93 2 10 Sleeve and Angle Installation Procedure Fig 10 10 1 This installation method is suitable for all wall structures the installat...

Страница 6: ...eparation instructions 11 2 This installation method is to be followed when extra support is required due to the damper size weight or other factors 11 3 Ensure that the supporting drop rods are suitably sized for the damper Refer Fig 8 11 4 Ensure that the drop rods are anchored fastened in the top supporting structure 11 5 Depending on wall thickness it may ease connection of ductwork if connect...

Страница 7: ...amper centrally in wall opening 12 5 Prepare 16 off pattress pieces from plasterboard of same material as main construction Plasterboard pattress should be sufficiently wide to butt up to damper spigots duct and overlap the outer edge of the track lining the opening by at least 10mm They need to be long enough to form neat corners 12 6 Two layers of pattress are required each side of wall and the ...

Страница 8: ...ring drive directions 16 3 Manually wind the actuator using the crank handle provided fully to the reset position and lock into position Due care should be taken to stop winding when slight resistance is encountered over winding can result in permanent damage to the damper actuator which may invalidate the warranty 16 4 Damper must be in closed position 16 5 Fit actuator cradle in desired orientat...

Страница 9: ...E END in 60 seconds Confirm visually that blade position and indication pointer on the actuator corresponds 20 11 If the damper has seized failing to reach either drive end or spring end 20 11 1 Isolate and remove actuator Refer to section 19 20 11 2 Spray a light lubricant into blade end bearings through the holes on the side gaskets 20 11 3 Using the 12mm A F spanner on the TD box Drive Shaft be...

Страница 10: ...ly appointed competent person 23 4 The installation needs to be inspected thoroughly before the damper actuation is tested 23 5 Actuation testing should be completed as follows 23 5 1 Isolate the power 23 5 2 Remove access door s 23 5 3 Test manually using the crank handle provided to set the damper to the normal state powered state A quarter turn in the opposite direction locks it Visually confir...

Страница 11: ...TTED BY Print name Signature Company Date FAIL SAFE POSITION POWER OFF position Tick appropriate box OPEN SHUT FINAL INSPECTION BY Print name Signature Company Date This document is available for free download from the BSB website This document is subject to change without notice BSB Engineering Services Ltd Tel 44 0 1795 422609 Email enquiries bsb dampers co uk website www bsb dampers co uk Dec 2...

Отзывы: