background image

Page 6 of 11 pages 

10.9 

There are 8off ‘angle’ pieces provided, 4off for the ‘sides’ and 4 for top/bottom of 
the sleeve. The ‘sides’ are identified with an ‘S’ close to the tabbed end of each 
piece. Be especially careful when the lengths of T/B nearly are same as the sides! 

10.10  Fit to one side of wall, 1

st

 angle assembly. Fit this to sleeve by positioning around 

sleeve, fitting tabs through slots, and bending tabs lightly with hammer to begin 
with, and when all are positioned correctly, and 1

st

 angle assembly is flush up to 

wall, knock all four down fully to secure. 

10.11  Rivet 1

st

 angle assembly to sleeve with 3mm min steel pop rivets at max 150mm 

centres  all  round,  tight  and  flush  against  surface  of  wall.  Check  gaps  (if  any) 
between angle and wall are less than 2mm. 

10.12  Fit  second  angle  in  similar  manner  to  1

st

  making  sure  both  angles  are  tight  up 

against wall surfaces and all gaps (if any) are less than 2mm 

10.13  Do not fix angles to wall, as damper should be free to move within opening. 
10.14  Connect ductwork as required. 

11  Dry wall 

– Cleated Installation Procedure – Fig. 11 

11.1 

Refer to section 5 for wall preparation instructions. 

11.2 

This installation method is to be followed when extra support is required due to 
the damper size (weight) or other factors. 

11.3 

Ensure that the supporting drop rods are suitably sized for the damper. (Refer Fig. 
8)  

11.4 

Ensure that the drop rods are anchored/fastened in the top-supporting structure. 

11.5 

Depending on wall thickness, it may ease connection of ductwork, if connecting 
ductwork is attached to damper prior to fabricating the wall. 

11.6 

Plasterboard  pattress  (16  off  piece  of  the  same  material  as  main  wall 
construction), should  be  sufficiently  wide  to butt  up  to  damper  spigots/duct  and 
overlap the outer edge of the track lining the opening by at least 10mm. They need 
to be long enough to form neat corners. 

11.7 

Two  layers  of  pattress  are  required  each  side  of  wall  and  the  corners  should 
‘overlap’ between the first and second layers. 

11.8 

Fit second pattress to other side of wall in similar manner. 

11.9 

Apply  intumescent  sealant  to  the  pattress  parts  and  fit  snugly  up  against  the 
spigot. 

11.10  It is not a necessity to fill the void between the pattresses, but it can be done for 

insulation purposes if desired. 

11.11 

Important:

 Ensure the drywall 

screws ‘pick up’ the track lining the hole, so that 

the proper fire integrity of the installation will not be compromised. 

Figs 10 

Содержание FSD-TD Damper

Страница 1: ...ding Control officer and or specifying authority 2 6 Refer to actuator label for wiring of actuator 2 7 Refer to section 20 for testing Complete Insp Check List at end of this document 2 8 For existing dry walls When cutting the opening for damper and partial removal of stud is unavoidable ensure the structure is sufficiently supported to conform to design specification 2 9 Dry wall openings must ...

Страница 2: ...e for TD drive box 5 3 2 Cut size nominal damper width 121mm 2 x wall board thickness by nominal damper height 96mm 2 x wall board thickness 5 3 3 Example for 500x300 damper and 12 5mm wall board cut hole should be 646mm x 421mm 500 121 2x12 5 x 300 96 2x12 5 5 4 Mark out the position and size of required cut size on the wall 5 5 Using appropriate means e g jig saw cut the hole in the wall removin...

Страница 3: ...he wall Make the hole in the wall Wall only Prepare a pair of spacing blocks approx 10mm high x 25mm square from any available material such as drywall boards Position spacing blocks within the opening at extremities of damper and stand the damper with blades running horizontally on blocks so that damper is central in opening Fix the angle frame to the wall using suitable expansion bolt steel slee...

Страница 4: ...he opening in corresponding positions to the HEVAC frame builder s ties 8 5 Bend the builder s ties out See Fig 5 8 6 Vertical installation only Prepare a pair of spacing blocks approx 25mm cubed from any available material such as drywall boards Position spacing blocks within the opening at extremities of damper and stand the damper on blocks so that damper is central in opening 8 7 While support...

Страница 5: ... sides overlap and affix 150mm wide strips of firebatt to form a pattress around the damper Fig 8 Drop rod load bearing specification Drop rod size Max load per pair of studs kg E60 E120 E240 M6 54 7 36 5 21 9 M8 100 4 66 9 40 2 M10 159 8 106 6 63 9 M12 233 1 155 4 93 2 10 Sleeve and Angle Installation Procedure Fig 10 10 1 This installation method is suitable for all wall structures the installat...

Страница 6: ...eparation instructions 11 2 This installation method is to be followed when extra support is required due to the damper size weight or other factors 11 3 Ensure that the supporting drop rods are suitably sized for the damper Refer Fig 8 11 4 Ensure that the drop rods are anchored fastened in the top supporting structure 11 5 Depending on wall thickness it may ease connection of ductwork if connect...

Страница 7: ...amper centrally in wall opening 12 5 Prepare 16 off pattress pieces from plasterboard of same material as main construction Plasterboard pattress should be sufficiently wide to butt up to damper spigots duct and overlap the outer edge of the track lining the opening by at least 10mm They need to be long enough to form neat corners 12 6 Two layers of pattress are required each side of wall and the ...

Страница 8: ...ring drive directions 16 3 Manually wind the actuator using the crank handle provided fully to the reset position and lock into position Due care should be taken to stop winding when slight resistance is encountered over winding can result in permanent damage to the damper actuator which may invalidate the warranty 16 4 Damper must be in closed position 16 5 Fit actuator cradle in desired orientat...

Страница 9: ...E END in 60 seconds Confirm visually that blade position and indication pointer on the actuator corresponds 20 11 If the damper has seized failing to reach either drive end or spring end 20 11 1 Isolate and remove actuator Refer to section 19 20 11 2 Spray a light lubricant into blade end bearings through the holes on the side gaskets 20 11 3 Using the 12mm A F spanner on the TD box Drive Shaft be...

Страница 10: ...ly appointed competent person 23 4 The installation needs to be inspected thoroughly before the damper actuation is tested 23 5 Actuation testing should be completed as follows 23 5 1 Isolate the power 23 5 2 Remove access door s 23 5 3 Test manually using the crank handle provided to set the damper to the normal state powered state A quarter turn in the opposite direction locks it Visually confir...

Страница 11: ...TTED BY Print name Signature Company Date FAIL SAFE POSITION POWER OFF position Tick appropriate box OPEN SHUT FINAL INSPECTION BY Print name Signature Company Date This document is available for free download from the BSB website This document is subject to change without notice BSB Engineering Services Ltd Tel 44 0 1795 422609 Email enquiries bsb dampers co uk website www bsb dampers co uk Dec 2...

Отзывы: