KJM MANDÍK
–
Detailed operating instructions
M&C KJMPNO 07/2022
MANDÍK, a.s.,
61
Supply
– sensor is located after the recuperator on the supply air and is applicable for
frost protection of the recuperator or for pool units.
HeatWaterTemperature
(
No
/
Extract
/
Supply
/
Both
)
– temperature sensor can be selected to
measure the water temperature of the water heater according to the measurement purpose.
The meaning of the configuration options is:
Extract
– sensor is designed to measure the temperature of the water at the drain
line, so-called return line.
Supply
– sensor is designed to measure the temperature of the water on the supply
pipe.
CoolWaterTemperature
(
No
/
Extract
/
Supply
/
Both
)
– temperature sensor can be selected to
measure the temperature of the cooling water according to the measurement purpose:
Extract
– sensor is designed to measure the temperature of the water at the drain
line, so-called return line.
Supply
– sensor is designed to measure the temperature of the water on the supply
pipe.
TemperatureExhaust
(
No
/
Extract
/
Exhaust
/
Both
)
– temperature sensor can be selected to
measure the temperature of the exhaust air according to the measurement purpose:
Extract
– sensor is designed to measure the temperature of the air exhausted from
the room.
Exhaust
– sensor is designed to measure the temperature of air exhausted to the
outside.
HumidityRegulation
(
No
/
DehumRel
/
HumRel
/
BothRel
/
DehumAbs
/
HumAbs
/
BothAbs
)
– defines
the humidity control methods:
DehumRel
– only dehumidification based on relative humidity is performed using one
of the cooling components or using fans and mixing dampers.
HumRel
– only humidification based on relative humidity is performed using a
humidifier.
BothRel
– system dehumidifies and humidifies as needed based on relative humidity.
DehumAbs
– only dehumidification based on absolute humidity is performed using
either of the cooling components or using fans and mixing dampers.