to achieve the required parameters. This regime of operation is usually used outside dwelling or
working hours.
The fan speeds are set in the
ComponentsMachine
Fans
menu via the
Economy
(80%)
variable for the supply and exhaust fans separately. The required temperature is set in the
ComponentsMachine
Temperatures
menu via the variable
Economy
(18 °C).
5.2.5
Comfort regime
In this operating regime, the AC unit is switched on in a regime where the required fan
speed is set to the comfort limit, and the required temperature is set to the comfort value for
summer and winter separately. The control controls the individual components (heating, cooling,
and humidification) to achieve the required parameters. This operating regime is usually used
during dwelling or working hours.
The fan speeds are set in the
ComponentsMachine
Fans
menu via the
Comfort
(100%)
variable for the supply and exhaust fans separately. The required temperature is set in the
ComponentsMachine
Temperatures
menu via the variable
Comfort
(22 °C).
5.2.6
Auxiliary regime
Information about the occurrence of an auxiliary regime is displayed with the
AM
symbol in
front of the current regime. The type of auxiliary regime itself is displayed at the end of the start
screen or at the end of the
ComponentsMachine
menu. The auxiliary regime occurs when a
situation arises that requires a temporary change in the operation of the AC unit, due to too high
or low temperature, failure of a component, non-standard operation of a component, protection
of the unit, etc. The following auxiliary regimes may occur:
CompenssationSpeed
– occurs when the supply temperature drops and compensation is
enabled for any of the options in the
ComponentsMachine
Fans
menu:
MixingCompensation
CompensationTemperature
CoolError
Defrost
HeatErr