Equipment components
The AC unit consists of individual mechanical components that ensure its required function
with the required parameters. Depending on the technical specification, these components are
configured in the measuring and control system and then displayed in item
ComponentsMachine
.
The components include, for example,
Temperatures
,
TemperatureRegulation
,
Fans
,
Burner
,
ElectricalHeating
,
WaterHeating
,
CondensingUnit
,
Recuperator
,
Dampers
,
Filters
, and others.
Every component displays its current performance or status. Selecting a component displays more
detailed information. Basic component information is available without logging in. These include
the following items:
State
(Off/……..) - informs about the status and required regime of operation. The specific
states may vary from component to component and are therefore described in detail for each
component.
Power
(%) – informs about the required output of the device.
OperatingHour
– may be used as information for service personnel due to wear and tear on
the fan or other components.
NumberStarts
– indicates how the unit is operated. A big number of starts may indicate
improper operation of the entire AC unit.
The following describes parameters that apply to most components and have the same
function, so they do not need to be described for every component separately. These parameters
can only be accessed after a service login:
PID–Regulation
(
BLOCK
/
OG
/
UG
/
REG
/
Y–NV
/
UDEF
)
– contains the control parameters that
determine the quality and speed of the required output control based on the required and
actual values. The values are set by default at the factory and should only be changed by a
person knowledgeable in control systems. The standard factory set values are shown for every
component. The meaning of the individual control states is as follows:
BLOCK
– controller function is not released,
OG
– forced maximum output, parameter
O,
UG
– forced minimum output, parameter
O,
REG
– controller is active,
Y–NV
– invalid setpoint, parameter
S
,
UDEF
– invalid output value, parameter
O.