KJM MANDÍK
–
Detailed operating instructions
M&C KJMPNO 07/2022
MANDÍK, a.s.,
43
State
– displays information about the gas heater operation.
Off
– water cooling is not used.
Cool
– water cooling is active.
Err
– water cooling pump is malfunctioning, the valve will close.
Power
(%) – current opening of the gas heating valve.
Pump
– displays information about the contact controlling the cooling pump.
Off
– water cooling pump contact is open.
On
– water cooling pump contact is open.
PID–Regulation
–
the factory default values are:
TI = 150 s, KP = 8, TD = 0 s.
CoolingWaterSupplied
( °C)
– current cooling water temperature upstream of the heat
exchanger.
CoolingWaterDrain
( °C)
– current temperature of the cooling water after the heat exchanger.
Condensing units
6.11
There are numerous manufacturers of external cooling devices on the market that can be
used with air conditioning units. Almost every manufacturer of a cooling or condensing unit has its
own control method. This causes a great deal of fragmentation in the way refrigeration or
condensing units are controlled, and sometimes it is very difficult to reconcile the control of an air
conditioning and condensing unit. Therefore, it is possible to choose the type of control of the
condensing unit (chiller) according to the specific control methods of each manufacturer, which is
continuously updated. The condensing unit control is prepared to control 6 separate units.
In the event of a failure or defrost of the condensing unit, the fan speed can be reduced to
reduce the supply air temperature to achieve the required supply air temperature. The
compensation for these conditions must be set in the menu
ComponentsMachine
Fans
.
This
condition is indicated on the controller display in the main menu as
AuxilieryMode
–
CompenssationSpeed
.
Unit
– displays information about the operation of the condensing unit.
Off
–
condensing unit is switched off.
Cool
–
condensing unit is operating in the cooling regime.
Heat
– condensing unit is operating in the heating regime.