KJM MANDÍK
–
Detailed operating instructions
M&C KJMPNO 07/2022
MANDÍK, a.s.,
17
CoolingWaterDrain
– this sensor can be configured if the unit contains a water cooler. It is
placed on the water exchanger discharge piping, called the return piping, so that it measures
the actual temperature of the cooling water. The sensor is for informational purposes only.
CoolingWaterSupplied
– this sensor is placed on the cooling water supply line to measure
the actual temperature of the water supplied to the water exchanger. The sensor is for
informational purposes only.
Recuperation
Inlet
– placed upstream of the recuperator on the air inlet.
Supply
– located after the recuperator on the air supply. Together with the inlet sensor, it
provides information on the current thermal performance of the recuperation
Extract
– ensures the correct defrost protection function of the recuperator. The
temperature sensor is placed behind the recuperator on the air outlet.
Extract
– temperature sensor is in many cases configured as a replacement for the room
temperature sensor, as it senses the temperature of the exhaust air from the room without
being affected by local room influences. It is placed in the exhaust duct.
Exhaust
– used to measure the temperature of the exhaust air. It is placed at the end of the
exhaust duct.
MoreRoomSensors
(
Average
/
OG
/
UG
/1/2/
SummerMin
/
WinterMin
)
– with multiple room
temperature sensors, determines how the final room temperature is calculated or assigned.
When 1, 2 is selected, the final room temperature is given only by the selected sensor, and
the other sensors are only informative. For other selections, the final value is calculated as a
mathematical average, maximum or minimum. The
SummerMin
option selects the lowest
measured room temperature in the summer and the highest in the winter. The
WinterMin
option selects the lowest measured room temperature in the winter and the highest in the
summer.
Display
(
Room
/
Extract
/
Supply
/
Preheat
/
Exhaust
)
– selects the temperature sensor whose
value will be displayed on the second line of the Home screen next to the current time. By
default, a reference temperature sensor is selected and compared to the required
temperature. A room, supply or exhaust air temperature sensor can be selected.