KJM MANDÍK
–
Detailed operating instructions
M&C KJMPNO 07/2022
MANDÍK, a.s.,
64
Press
– used to sense the air pressure and the amount of air in the duct supplied by
the fan. The
AssignmentInputs/Outputs
Fans
displays the assignment of a
separate input for the pressure sensor and flow sensor.
Direct
– fixed voltage value of the required speed 0-10V. The fan speed is set to this
value converted to a percentage of 0-100%.
POLv1
– six-step speed value entered from the POL822 room unit within the range of
values for
MinSpeed
and
Comfort
is used to control the fan speed
POLv2
– linear % speed value entered from the POL822 room unit within the range of
values for
MinSpeed
and
Comfort
is used to control fan speed.
AMR
– fan speed control is controlled by a linear % speed value entered from the
AMR-OP70 or AMR-OP41 room unit within the range of values for
MinSpeed
and
Comfort
.
BackupFans
(
No
/
Supply
/
Extract
/
Both
)
– activates the backup fans when the main fans fail:
Supply
– backup supply fan is activated when the supply fan fails.
Extract
– the exhaust fan fails, the backup exhaust fan is turned on.
Recuperation
(
No
/
Plate
/
Rotary
/
Glycol
/
RotaryFbk
)
– specifies the type of recuperator used
and its characteristics:
Plate
– plate recuperator with bypass damper without monitoring its position.
Rotary
– rotary recuperator with frequency converter controlled by digital and
analog controller outputs or stepper motor.
Glycol
– recuperation implemented by a glycol circuit.
RotaryFbk
– rotary recuperator with a sensor monitoring the recuperator speed.
WaterHeating
(
No
/1/2
)
– selection of the number and function of water heating:
1
– selection of standard water heating or in the preheating function. Temperatures
are configured for this water heating in
HeatWaterTemperature
.
2
– selection of the water heating in the preheating function. Temperatures are
configured for this water heating in
2HeatWaterTemperature
.
Boiler
(
No
/
Yes
)
– control of the boiler room to prepare heating water for water heating.
ElectricalHeating
(
No
/1/2
)
– selection of the number and function of electric heating:
1
– selection of standard electric heating or in preheat function.
2
– selection of electric heating in the preheating function.