TROUBLESHOOTING

TROUBLESHOOTING

Code

Desc.

Reason

Solution

E.SPD

Rapid failure

Controller application

Seek technical support from manufacturer

Improper setting of relevant  
parameters for rapid detection

Adjust rapid detection threshold and F10.45  
(rapid detection time)

Fan fault

Make sure that the fan is running normally.  
If not, replace the fan and start up again

Note:

 the percentage of output motor speed relative to F01.10 (maximum frequency) is greater than F10.44 (rapid detection 

threshold), and the fault is reported after continuous F10.45 of rapid detection time. By F10.43 (the rapid protection action),  
the fault detection and the motor operation mode can be set when the fault is detected.

Code

Desc.

Reason

Solution

E.TExx

Self-learning

failures

The output current of the 
controller exceeds the
upper and lower limits

Check if the motor connection is correct, reset and  
retry self-learning. If the error still occurs, contact  
the Mammoth Fan support team. 

Note:

 where “xx” is self-learning faults ub code.

Code

Desc.

Reason

Solution

E. oUxx

Mid 

acceleration/

moderate/ 

midspeed/

stop/over

-voltage fault

High voltage

Reduce the supply voltage to a specified range

Controller output or motor
short circuit

Check main circuit wiring, eliminate short circuit

Too short acceleration/ 
deceleration time

Determine whether the acceleration stops. The fault
detection increases F01.22 (acceleration time 1) 
increases F01.23 (deceleration time 1)

Overvoltage suppression of
frequency rise may result in
accelerated overvoltage fault

Increase overvoltage suppression gain F10.13

Over-current suppression  
of frequency-lowering
overvoltage fault

Decrease overcurrent suppression gain  
F10.02 and reduce load

Surge voltage mixed  
with input voltage

Add reactor to input side

Improper setting of speed
tracking parameters

Change of speed tracking parameter (F07.25~F07.28)

Note:

 this fault is detected when the bus voltage exceeds the overvoltage point. Three phase input overvoltage point is 820 V,

single-phase input overvoltage point is 400 V.

Содержание COMMERCIAL II Series

Страница 1: ...114 07 C A U T I O N R E A D I N S T R U C T I O N S C A R E F U L LY F O R S A F E I N S T A L L A T I O N A N D F A N O P E R A T I O N C O M M E R C I A L I I S E R I E S I N S TA L L AT I O N O PE...

Страница 2: ...ensure that they do not play with the appliance 6 An all pole disconnection switch must be incorporated into the fixed wiring in accordance with local wiring rules 7 The structure to which the fan is...

Страница 3: ...m cover 5 Aluminium alloy bushing 12 Blade components 6 Coil of wire 13 Extension tube 7 Fan controller CASE NO DIMENSIONS LxWxHmm Volume m3 Gross weight kg Remark 1 1400 x 600 x 310 0 16 70 Main body...

Страница 4: ...Exclusively distributed by Beacon Lighting 7 6 5 Required installation tools PARTS LIST ADJUSTABLE WRENCH LASER DISTANCE MEASURE ALLEN KEYS WIRE CUTTER SOCKET WRENCH LEVEL MULTIMETER SCREW GLUE...

Страница 5: ...r to the below diagram for detailed spacing requirement Secure the hanging bracket to the ceiling joist or structure with provided bolts and nuts Ensure there are 3 4 threads left on the bolt after ti...

Страница 6: ...propriate electrical connection to the fan body ensure neat and tight connections are completed NOTE This is the steel wire bracket Please make sure it is installed before installing the fan motor par...

Страница 7: ...FACE FUNCTION CODE DESCRIPTION EXPLANATION S00 Return Function can be used to return to the main interface If it doesn t return by this function it will automatically return to the main interface afte...

Страница 8: ...s this could damage the fan and cause a safety issue 3 Ensure that the fitting does not come in contact with any organic solvents or cleaners 4 The motor has a permanently lubricated ball bearing whic...

Страница 9: ...overcurrent fault Overload Reducing load or replacing impulse load of large capacity controller requires reducing load change frequency or replacing larger capacity controller Short circuit to the out...

Страница 10: ...ncrease Torque lift set too large Decrease F04 01 torque increase V F curve setting is not appropriate To determine the relationship between voltage and frequency of V F curve setting modify F04 00 VF...

Страница 11: ...arning If the error still occurs contact the Mammoth Fan support team Note where xx is self learning faults ub code Code Desc Reason Solution E oUxx Mid acceleration moderate midspeed stop over voltag...

Страница 12: ...major failure Mammoth Fans cannot be held responsible for any repair other than those carried out by it or one of its Authorised Service Agents Please keep this warranty information in a safe place Th...

Страница 13: ...C O M M E R C I A L I I S E R I E S...

Отзывы: