Page
10
of
36
from 0,2
O
C to 10
O
C, every
0,2
O
C – in the scope from -10
O
C
to +100
O
C
from 1,0
O
C to 10
O
C, every
1,0
O
C – in the scope <-10
O
C and
>+100
O
C
minimum operation time of the
chiller (unit)
CA
0 – inactive
1 – active; setting the time from
1 min. to 60 min., every 1 min.
0
maximum operation time of the
chiller (unit)
2
CC
0 – inactive
1 – active; setting the time from
0,5 h to 9,5 h, every 0,5 h
0
minimum standstill time of the
chiller (unit)
CF
0 – inactive
1 – active; setting the time from 1
min. to 60 min., every 1 min.
0
AF
function not available to the installer
/ user
3
stirrer operation mode
F0
0 – operation according to the times
set in E1 and E2, independent of the
operation of the chiller (unit)
1 – continuous operation during
the chiller (unit) operation, while
during the standstill of the chiller
(unit), the stirrer works according
to times set in E1 and E2
2 – unavailable
3
3 – unavailable
3
4 – continuous operation,
independent of the chiller operation
and times set in E1 and E2
1
stirrer standstill time
E1
setting the time from 1 min. to 60
min., every 1 min.
15 (min.)
stirrer operation time
E2
setting the time from 1 min. to 60
min., every 1 min.
2 (min.)
stirrer manual operation
4
CP
0 – continuous operation
>0 –operation for a specified time
from 1 min. to 60 min., every 1 min.
5 (min.)
delay time of registering
the maximum and minimum
temperatures
and delay time of switching on the
temperature alarm
AA
setting the time from 0 h to 24 h,
every 0,1 h
2 (h)
lower alarm temperature
A1
setting the temperature from -40
O
C
to +98
O
C
2 (
O
C)
upper alarm temperature
A2
setting the temperature from -40
O
C
to +98
O
C
12 (
O
C)
alarm sound
HE
0 – active
1 – inactive
0
alarm system (visual and audible)
of exceeding the set temperature
range (A1 and A2)
HA
0 – active
1 – inactive
0