MAJORSINE2000i-48-2U
DC Input
Voltage
40-60 VDC
Rated Current
50 Amps
Protection
Fuse and DC Breaker
Efficiency
>85% (full linear load),
48 VDC I/P, 230 VAC O/P
AC Output
Capacity
2KVA / 1600W
Voltage
208, 220, 230, 240 VAC
Voltage Regulation
±2%
Frequency
50/60Hz ± 0.2Hz
Wave Form
Pure Sine Wave
THD (linear load)
3% 120 V/100%
THD (SPS load)
5% 120 V/100%
Crest Factor
3:1
Receptacles
(4) IEC 320 outlets – C13
Utility Power (Bypass)
Voltage
Nominal 230 VAC
Frequency
50/60± 5 Hz
Protection
AC Circuit Breaker
Protection
Short
For 1 second; Switch to
Bypass, then shutdown
Overload
105-125% for 3 minutes
126-150% for 3 seconds
>150% for 1 second;
Switch to bypass
Temperature
55±5º(Inside the case)
Safety
Safety
CE Approved
EMI / RFI
FCC Class A
Mechanical
Dimensions
17.32”W x 11.81”D x 3.46”H
(440x300x88mm)
2U Rackmount
Weight
8kg / 17.6 lbs