7. COMMUNICATION
7-1 Dry Contact Communication Terminal
The “Dry Contact” terminal is the interface for two Form C
relays. The relays are used for switching the voltage provided
by the user’s external alarm system.
One contact set is for “DC Abnormal” and the other one is for
“FAULT”. When alarms in each classification trigger, the relay
switches state. (Ref: Sec. 6-3 Alarms) Connection to the
terminal should be made to external sensor circuits with
appropriate sized wire. The terminal can support 5A / 250VAC
in either NC or NO configurations.
¾
NC: Normally Closed
¾
CO: Common
¾
NO: Normally Open
7-2 SNMP Expansion Card Slot (WEB)
Remote monitoring is a prime consideration and requirement to
manage multiple network elements from a central location. SNMP
remote access as easy as; installing the plug-n-play card, configuring
your network IP address, and attaching the network interface cable.
The SNMP Kit includes:
¾
Interface electronics card
¾
Cover plate
¾
RS-232 to RJ-45 custom cable
¾
Quick installation guide
¾
CDROM with utilities and MIB
The integrated expansion card slot is located on the rear of the
inverter behind a protective cover plate. [Ref: 3-4 Rear Panel]
Installation of the SNMP card and cover plate is easily achieved using
a standard #2 cross point screw driver. Card IP address
programming required PC interface. Instructions for installation are
included in the kit.
(kit sold separately)