MAJORSINE Inverter Manual / M101.4
Page 16
¾
Use the following recommended cable sizes when connecting
power to the inverter.
Model
Capacity DC Input AC Input
AC Output
MAJORSINE1000-24-2U
1 KVA
#6 AWG #14 AWG
NEMA 5-15R
MAJORSINE1000-48-2U
1 KVA
#10 AWG #14 AWG
NEMA 5-15R
MAJORSINE2000-48-2U
2 KVA
#6 AWG #12 AWG
NEMA 5-20R
MAJORSINE1000i-48-2U
1 KVA
#10 AWG #14 AWG
IEC-320
MAJORSINE2000i-48-2U
2 KVA
#6 AWG #12 AWG
IEC-320
MAJORSINE1000-125-2U
1 KVA
#12 AWG #14 AWG
NEMA 5-15R
MAJORSINE2000-125-2U
2 KVA
#12 AWG #12 AWG
NEMA 5-20R
4-3 Installation Tool Kit
Contents of the tool kit include:
x
Poly zip bag containing twelve M4 screws and two
6-32 screws,
x
Two large mounting brackets (23” or 24” rack mount),
x
Two small mounting brackets (19” rack mount),
x
One protective cover for AC input,
x
One RS232 Cable.
4-4 Locking Hardwire Adapter
¾
The optional adapter is a reliable locking NEMA 5-15 plug on
one end and terminal screws on the other end. The
plug-to-terminal conversion is used to secure bare wire load
circuit wiring to the output sockets of the inverter. The adapter
includes strain relief for the wires being connected to the
terminals.