Bypass Utility AC Alarm Thresholds
For 100VAC system
O/P = 100Vac O/P = 110Vac O/P = 115Vac O/P = 120Vac
AC Bypass Voltage
Range
80Vac ~
120Vac
90Vac
~130Vac
95Vac ~
135Vac
100Vac
~140Vac
AC Bypass Frequency
Range F=50Hz
45.5Hz ~ 54.5Hz
AC Bypass Frequency
Range F=60Hz
55.5Hz ~ 64.5Hz
AC Bypass Recovery
From Over Voltage
115Vac
125Vac
130Vac
135Vac
AC Bypass Recovery
From Under Voltage
85Vac
95Vac
100Vac
105Vac
For 200VAC system
O/P = 208Vac O/P = 220Vac O/P = 230Vac O/P = 240Vac
AC Bypass Voltage
Range
188Vac
~228Vac
200Vac
~240Vac
210Vac
~250Vac
220Vac
~257Vac
AC Bypass Frequency
Range F=50Hz
45.5Hz ~ 54.5Hz
AC Bypass Frequency
Range F=60Hz
55.5Hz ~ 64.5Hz
AC Bypass Recovery
From Over Voltage
223Vac
235Vac
245Vac
255Vac
AC Bypass Recovery
From Under Voltage
193Vac
205Vac
215Vac
225Vac