7. Environmental conditions and operating limits
10
Environmental conditions and
operating limits
Permitted maximum air tempe 40 °C.
The domestic air supply must be set up so
that virtually no air can flow into the living
areas from the kitchen, bathroom or WC.
A room from which the air has to be extracted
must be fitted with a non-closable, free supply
air cross section of at least 150 cm²,
e.g.
with Maico door ventilation grille MLK.
ER EC units have resistance to interference
in line with EN 55014-2 (depending on pulse
shape and an energy factor of 1000 to 4000
V). These values can be exceeded when
operating with fluorescent tubes. In this case,
additional interference suppression measures
(L, C components or RC module, protection
diodes, varistors) are required.
7.1 Regulations for operation with
fireplaces
For operation with
air-ventilated fireplaces,
sufficient supply air intake
must be
ensured. The maximum permitted pressure
difference per residential unit is 4 Pa.
The fan may only be installed in residential
units with air-ventilated fireplaces if:
●
the evaluation criteria drawn up by the
responsible, regional master chimney
sweep are met;
●
a parallel operation of air-ventilated
fireplaces for liquid or gaseous fuels and
the air-extracting equipment can be
prevented, or
●
the extraction of exhaust gas from the air-
ventilated fireplaces is monitored by
special safety equipment. The ventilation
system or the fireplaces must be switched
off if the equipment is triggered.
Technical data
For technical data,
the rating plate [T].
For characteristic curves
Internet.
Rated voltage
230 V
Power frequency
50 Hz
Power consumption:
ER EC and ER-A
ER-AK, ER-AH and ER-AB
3/5
W*
2/2,5/
3
/
5
/17W*
Degree of protection
IP X5
Sound power level L
WA7
19 to
52 dB(A)
Mains cable to ER EC,
depending on switching
variant for
ER-A, ER-AK, ER-AH, ER-AB
3 x 1.5 mm²
or
5 x 1.5 mm²
Weight
ER GH housing
ER EC fan insert
ER-A.. cover
0.6 kg
0.72 kg
0.6 kg
* Specification according to DIN
18017-3 with
an equivalent absorption area of A
L
= 10 m
2
Storage
Only store ER EC covers in a suitable, dry
room. Ambient temperature - 10 °C to + 60 °C.
Maico accepts no liability for corrosion
damage caused by improper storage,
e.g. storage in damp surroundings.