background image

10. Fan insert 

 

12 

10.2 Commissioning 

1.  Switch on mains fuse and remove warning 

sign. 

2.  Run function test.  
3.  Check that the fan is running smoothly. 
4.  During the shell phase, switch off mains 

fuse, secure against being accidentally 

switched back on and position a visible 

warning sign. 

 

10.3 Removing fan insert 

1.  Before removing the fan insert, switch off 

all supply circuits (switch off mains fuse), 

secure against being accidentally switched 

back on and position a visible warning 

sign. 

2.  Remove the ER-A.. cover. To do so, 

swivel the upper part of the cover 

upwards, remove air filter [17], unscrew 

the central screw [16] and carefully 

remove the entire upper part. 

3.  Press the 3 locking hooks [X] of the stud 

[11] and evenly pull the fan insert out of 

the housing in parallel. 

 

 

The degree of protection, according 

to the rating plate, is only ensured in 

case of proper installation (fan insert 

correctly engaged). 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 Installing the cover 

ER-A, ER-AK, ER-AH, ER-AB

 

 

It is possible to rotate the cover by 

± 5° to compensate for housings 

which have been fitted at an angle. 

1. 

ER-AK, ER-AH, ER-AB: 

Pull off the 

sealing plugs [12] from the motor board 

interface (

 Fig. 2). Plug flat channel with 

plug of the ER cover in the interface 

connector. Ensure correct connection. 

2. 

ER-A, ER-AK, ER-AH, ER-AB:

 

Screw cover to the fan insert with the 

central screw [16]. If installing on a wall, 

ensure that the Maico name is on the 

bottom right. 

3.  Insert the air filter [17] and fold down the 

upper part of the cover (upper part must 

audibly engage). 

4.  Run function test: Test all unit functions 

(overrun time, interval, humidity control 

etc.). 

 

For ER-A, no setting function. 

For ER-AK, ER-AH, ER-AB, all 

operating parameters can be 

changed. 

Содержание ER-A

Страница 1: ...Mounting and operating instructions ER EC covers For ER EC recess mounted exhaust air systems according to DIN 18017 3 ER A ER AK ER AH ER AB www m aico ventilatoren c om UK...

Страница 2: ...2 1...

Страница 3: ...nings 5 Operating the fan 7 System and product information 7 6 1 Certificates of approval 7 6 2 ER EC covers 7 6 3 ER EC functions 9 Environmental conditions and operating limits 10 7 1 Regulations fo...

Страница 4: ...r part of cover central screw air filter these mounting and operating instructions For accessory components chapter 16 with more detailed information and order numbers Specialist installer qualificati...

Страница 5: ...explosion Risk to health from chemicals or aggressive gases vapours Chemicals or aggressive gases vapours may harm health especially if they are distributed throughout the rooms by the fan Never use...

Страница 6: ...nted Electric components are a potential source of electric shock If the unit is open all off the supply circuits must be switched off mains fuse off secured against being accidentally switched back o...

Страница 7: ...In the event of overload blocking the fan switches off automatically Ensure sufficient supply air during operation System and product information 6 1 Certificates of approval Certificates of approval...

Страница 8: ...r change display ER AH cover Model with humidity control and time module like ER AK Barrier free product In automatic mode the fans switch on when the humidity value limit is exceeded and switches off...

Страница 9: ...base load and full load levels can be set Additional air volumes that can be set in base load 20 m h 40 m h and full load 100 m h Full load level on off via light switch or separate switch During manu...

Страница 10: ...in residential units with air ventilated fireplaces if the evaluation criteria drawn up by the responsible regional master chimney sweep are met a parallel operation of air ventilated fireplaces for l...

Страница 11: ...uction soiling if necessary 3 Check wiring diagram sticker for correctness of the ticked fan type 4 Check ease of movement of shutter When installed it must close automatically 5 Check that connection...

Страница 12: ...of the housing in parallel The degree of protection according to the rating plate is only ensured in case of proper installation fan insert correctly engaged Installing the cover ER A ER AK ER AH ER...

Страница 13: ...ime has expired the filter change LED blinks red every 5 sec To reset the filter change interval push the RESET button for 2 seconds As a confirmation the filter change LED flashes 1x briefly A new RE...

Страница 14: ...have to be specified manually If the relative humidity falls below the reference value during operation the newly established reference value is saved The lowest possible reference value is 45 relativ...

Страница 15: ...not use aggressive cleaning agents 1 Clean ER A cover only with a dry cloth 2 If the cover is very dirty remove it and clean with water 13 1 Filter change Change the air filter when ER A bar B is comp...

Страница 16: ...lt Cause measure Fan output inadequate Dirty filter Replace filter Locking hook not engaged Engage fan insert correctly Incorrect duct diameter Check duct diameter of the main duct Supply air cross se...

Страница 17: ...splay TimeStrip ZF EC replacement air filter for ER AK ER AH and ER AB article no 0093 0758 5x ZF EC replacement air filter filter class G2 Large pack of ZF EC replacement air filters for ER AK ER AH...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...Maico Elektroapparate Fabrik GmbH Steinbeisstr 20 78056 Villingen Schwenningen Germany Service 49 7720 6940 info maico de D08 18_UK_DSW AS...

Отзывы: