©
2006 Magnum Energy Inc
.
AC IN
(Hardwire versions)
AC OUT
(Hardwire versions)
Strain
relief’s
AC
Ground
(In & Out)
Neutral
In
Hot
Out
Neutral
Out
Hot
In
Figure 11, AC Wiring Connections
AC Input Wiring
Your inverter has an AC transfer feature that passes the AC input
power to the inverter’s output. Connection to the AC input is made by
hardwiring from a distribution panel as described below:
1. Run an appropriately sized 2-conductor plus ground cable (from
the AC distribution panel) through a strain-relief on the AC IN
opening. Refer to Table 4 for minimum wire size and overcurrent
protection required for the AC input wiring.
2. Remove about two inches of the insulating jacket from the AC
cable and separate the three wires and strip about 3/4” of insulation
from each wire.
3. Using an approved AC wire connectors, connect the incoming Hot
In, Neutral In and Ground wires to the MM Series AC wires colored
black (HOT IN), white (NEU IN) and green (AC GROUND) respectively.
4. After making the AC input connections, secure the AC input cable
by tightening the strain relief.
The AC input wiring in the inverter is complete, review all AC wiring
to ensure all connections are correct and secure.
19
2.0 Installation
http://www.wholesalesolar.com/inverters.html
http://www.wholesalesolar.com/inverters.html