26
58-610 Model R82 Radar Transmitter
2.6.6.2 Radar Transmitter User Menu—Volume and Level
Note: Press UP arrow 5 times to reach screen where menu language can be chosen.
Display
Action
Comment
1
*Status*
*Level*
*Volume*
*Distance*
*Echo Str xx*
*%Output*
*Loop Current*
*Local Tag*
Transmitter Display
Transmitter default display: Status, Level, Distance,
Echo Strength, % Output, Loop Current and Local Tag values
advance every 2 seconds. All screens (except 2-8) default to
this screen after 5 minutes of no keystrokes or if a Fault or
Warning message is displayed.
Default display will also show the highest priority Fault or
Warning. If more than one Fault or Warning exists they will be
displayed in the History screen (Item #2, Section 2.6.6.4
Radar
Transmtter Factory Menu
on Page 40) in chronological order.
To Add/Remove what information is shown in default display:
• Go to specific parameter in question (screens 2-8)
• Press Enter
• Choose On or Off
• Press Enter to confirm
2
Level
xxx.x units
Transmitter Display
Transmitter displays Level measurement in chosen unit of
measure.
3
Volume
xxx.x units
Transmitter Display
Transmitter displays Volume measurement in chosen unit of
measure.
4
Distance
xxx.x units
Transmitter Display
Transmitter displays Distance measurement in chosen unit of
measure; measurement includes Sensor Offset value. This value
may not represent reciprocal of Level if the liquid level is
within the Blocking Distance or Level Offset where the Level
value is clamped.
5
Echo Strength xx
xxx.x units
Transmitter Display
Transmitter display showing Level and Echo Strength of signal
reflection. Good values are 20-99.
6
% Output
xx.x%
Transmitter Display
Transmitter displays % Output measurement derived from
20 mA span.
7
Loop Current
xx.xx mA
Transmitter Display
Transmitter displays Loop Current value (mA).
8
Local Tag
xxxxxxxxxxxx
Transmitter Display
Transmitter displays Local Tag information.
9
Measure Type
(select)
Select Type of Measurement
Select
Level Only
or
Flow & Level
,
Volume & Level
,
Flow
,
Flow Units
,
Volume
,
Volume Units
,
Loop Control
, and
Strapping Table
screens appear when necessary. Note that
the Flow or Volume screens are selected for rotation when
Measure Type is set to
Flow & Level
or
Volume & Level
and is
deselected when Measure Type is set to Level Only.
See Section 2.6.6.1 for the complete Level menu or 2.6.6.3 for
the complete Flow and Level menu.
10
Level Units
(select)
Select Units of measure
Select cm (xxxx), meters (xx.xx), inches (xxx.x), or feet (xx.xx).
Allowable decimal position is controlled; four characters is
maximum reading. Decimal position is controlled by Units
and Tank Height.
11
Sensor Offset
xx.x units
Enter the Sensor Offset value
Sensor Offset is the distance (+ or -) from the Sensor reference
point (bottom of NPT thread or flange face, top of BSP thread)
to the top of the tank.
12
Tank Top
(select)
Enter the shape/type
of tank top
Select the metallic tank top structure Flat, Horizontal Cylinder,
Dome, Irregular, or Other (non-metallic).
13
Tank Height
xxx.xx units
Enter the Tank Height
Tank Height is distance from the bottom to the top of the tank.