16
58-601 Pulsar
®
Radar Transmitter
Red (+)
Black (-)
(+)
(-)
NOTE: ALWAYS RUN THE TARGET REJECTION ROUTINE AFTER
MAKING CHANGES TO MENU CHOICES (
Antenna Type
,
Antenna Mount, Sensor Offset, Tank Height, Blocking
Distance, Dielectric, Turbulence, Rate Change, Foam
) or
when launcher is repositioned.
2.5
Wiring
Caution
The PULSAR Radar transmitter operates at voltages of
16–36 VDC (GP), 16-28.6 VDC (IS) and 16–36 VDC (XP).
Higher voltage will damage the transmitter.
Wiring between the power supply and the Radar transmitter
should be made using 18–22 AWG shielded twisted pair
instrument cable. Within the transmitter enclosure, con-
nections are made to the terminal strip and the ground
connections. The directions for wiring the Radar transmitter
depend on the application:
• General Purpose or Non-incendive (Cl I, Div. 2)
• Intrinsically Safe
• Explosion Proof
NOTE: For ATEX/IEC installation guidelines refer to bulletin BE 58-601.
WARNING!
Explosion hazard. Do not remove covers unless power
has been switched off or the area is known to be non-
hazardous.
2.5.1 General Purpose or Non-incendive (Cl I, Div. 2)
A general purpose installation does not have flammable
media present. Areas rated non-incendive (Cl I, Div. 2) have
flammable media present only under abnormal conditions.
No special electrical connections are required. If flammable
media is contained in the vessel, the transmitter must be
installed per Cl I, Div. 1 standards of area classification.
To install General Purpose or Non-incendive wiring:
1. Remove the cover to the wiring compartment of the trans-
mitter. Install the conduit plug in the unused opening.
2. Install a conduit fitting and pull the supply wires.
3. Connect shield to an earth ground at power supply and
leave floating at the transmitter.
4. Connect an earth ground wire to the nearest green ground
screw per local electrical code (not shown in illustration).
5. Connect the positive supply wire to the (+) terminal and
the negative supply wire to the (-) terminal.
6. Replace cover to the wiring compartment of transmitter.
2.5.2 Intrinsically Safe
An intrinsically safe (IS) installation potentially has flam-
mable media present. An approved IS barrier must be
installed in the non-hazardous (safe) area.