background image

I/O Start up the device
1

Enter DEVICE SET UP
Press one of the following alphanumeric keys (if no key is sensed after 5 s, the
unit will automatically jump to RUN mode and alternatively show Level/% Output
and Loop signal

1 for entering CALIBRATION (see page 5 for additional information)
2 for entering BASIC SETUP – general HART
3 for ADVANCED SET UP CONFIGURATION (see page 5 for additional infor-

mation)

4 for entering DIAGNOSTICS (see page 5 for additional information)
5 for entering REVIEW to review all settings.

CALIBRATION USING HART

®

IMPORTANT: Check whether your HART

®

communicator is equiped with the 805 Device Descriptors (DD’s). Older pur-

chased devices may require an update – consult your local HART Service Centre or Magnetrol for further assistance.

IMPORTANT: The digital HART

®

communication is superimposed on the 

4-20 mA loop and requires a min. load resistance of 250 

and a max load

resistance of 450 

.

+

+

-

-

Junction

Control

Room

Display

Power
Supply

Current
Meter

250 

< R

L

< 450 

CONNECTIONS

Connection of your Hart communicator:
• at power terminals (+) and (-) in wiring compartment
• at first junction box between unit and control room.

HART MENU

1 Device Setup

2 Level

3 % Output

4 Loop

1 Units

2 Empty Calibration

3 Full Calibration

4  4 mA Set Point

20 mA Set Point

6 Damping

7 Fault State

8 Date/Time/Initials

1 Model

2 Manufacturer

3 Dev Id, S/N

4 Tag

5 Descriptor

6 Date

7 Message

8 Units

9 Cap at empty Cal

10 Cap at full Cal

11 4 mA Set Point

12 20 mA Set Point

13 Damping

14 Fault State

15 Date/Time/Initials

16 Final Asmbly Num

17 Universal Rev

18 Fld Dev Rev

19 Software Rev

20 Poll Address

21 Num Req Preams

22 Firmware Version

1 Tag

2 Descriptor

3 Date

4 Message

5 Final Asmbly Num

6 Poll Address

7 New Password

1 Adjust Trim 4 mA

2 Adjust Trim 20 mA

3 4 mA Trim Value

4 20 mA Trim Value

5 Enter Password

6 Set Magnetrol S/N

7 Set Dev ID Number

1 Loop Test

2 Error Codes

3 Probe Reading

4 Cap at empty Cal

5 Cap at full Cal

1 3.6 mA

2 4 mA

3 20 mA

4 22 mA

5 Other

1 Calibration

2 Basic Setup

3 Advanced Setup/

Configuration

4 Diagnostics

5 Review

6

Содержание KOTRON SMART RF 805

Страница 1: ...R F Capacitance Level Measurement Installation and Operating Manual KOTRON SMART RF MODEL 805 TRANSMITTER...

Страница 2: ...and record the serial number for future reference when ordering parts MOUNTING Nameplate partnumber amplifier serial n tag n 2 cable entries one plugged M20 x 1 5 3 4 NPT or PG 13 5 Handtighten or us...

Страница 3: ...local current meter Ex Non Ex Ex Non Ex Ex Non Ex CAUTION ALWAYS check for proper grounding Improper grounding will cause malfunction of the unit CALIBRATION NOTE When connected to an approved barrie...

Страница 4: ...nt is the highest level from which the calibration is performed Hi Cal is measured from the end of the probe Lo Cal cm or inches Low Calibration point is the lowest level from which the cal ibration i...

Страница 5: ...single transmitter installation Fine tune the 4 mA point Attach a mA meter to the output If the output does not equal 4 0 mA adjust the value on the display to equal 4 00 mA Fine tune the 20 mA point...

Страница 6: ...oom Display Power Supply Current Meter 250 RL 450 CONNECTIONS Connection of your Hart communicator at power terminals and in wiring compartment at first junction box between unit and control room HART...

Страница 7: ...y HART software does not Contact manufacturer of your HART information e g Mfgs ID Device account for Mfgs ID s greater master software for upgrade This is a Serial etc but will not read any than 63 M...

Страница 8: ...3 003 Housing cover blind 316 SST Consult factory 5 Housing cover with glass 36 4410 001 Housing cover with glass 316 SST Consult factory 8 APPROVALS Agency Description ATEX II 1G EEx ia IIC T4 ambien...

Страница 9: ...Electronic Module Yes Yes Yes Yes Yes Yes Yes No No No No No No Display has Text No Reseat Boards Check Power Supply and Wiring Loop Resistance Wrong Correct Loop Resistance Start Good Display No Act...

Страница 10: ...lure to Operate with Correct Loop Inputs Display Working Yes No Retest Unit Good Display Key Board Responds Replace Electronic Module No Check Loop Current at Wiring Board Loop Current 22 4 0 mA Adjus...

Страница 11: ...heck Calibration Parameters Yes Yes Yes Corrupt Display Text Replace Electronic Module No Yes Replace Electronic Module Same Error Message Retest No Yes Active HART Analog Loop Correct Trim 4 20mA Che...

Страница 12: ...Material Aluminium A356T6 0 25 copper or 316 SST 1 4401 IP 65 Net and Gross Weight 2 70 kg net 3 20 kg gross Overall Dimensions H 214 mm 8 43 x W 111 mm 4 38 x D 188 mm 7 40 FUNCTIONAL PHYSICAL Descri...

Страница 13: ...e view Optional Mounting Flange 3 4 NPT 1 NPT 1G 1 BSP Optional Mounting Flange Optional Anchor Assembly Optional Weight 13 0 50 bare probe 16 0 625 insulated probe 5 0 1875 6 0 2500 75 2 95 34 1 32 1...

Страница 14: ...X II 1G EEx ia II C T6 A complete measuring system consists of a 1 Smart R F KOTRON 805 amplifier 2 KOTRON Probe a full range of rigid and flexible probes for conductive and non conductive media is av...

Страница 15: ...15...

Страница 16: ...Material Authorisation RMA form will be obtained from the factory It is mandatory that this form will be attached to each material returned This form is available through Magnetrol s local representat...

Отзывы: