MAINTENANCE

TROUBLESHOOTING SYSTEM PROBLEMS – LCD version

Symptom

Problem

Solution

LEVEL, % OUTPUT and LOOP values

Basic configuration data is

Check values and recalibrate if 

are all inaccurate.

questionable.

necessary (either or both points).

LEVEL readings are repeatable but

Configuration data does not

Recalibrate if necessary.

consistently high or low from actual

accurately match tank height.

by a fixed amount.

LEVEL, % OUTPUT and LOOP

Turbulence.

Increase the Damping factor until the

values fluctuate.

readings stabilize.

LOOP value jittery, usually in tenths

Factory settings corrupted.

Check # of Ticks. If the number is

or hundredths digit.

also jittery, consult the Factory.

HART device only: handheld will only

Most current Device Descriptors

Contact local HART service center for

read Universal Commands.

(DDs) are not installed in handheld.

the latest DDs.

HART device only; reads Product

Early HART software does not

Contact manufacturer of your HART

information (e.g., Mfgs. ID, Device #,

account for Mfgs. ID #’s greater

master software for upgrade. This is a

Serial #, etc.) but will not read any

than 63. Magnetrol’s ID is 86.

shortcoming of early HART master

process variables.

software.

OSC FAIL

malfunctioning analog board and/or

Check connection between electronics

(HART error code = 0x40)

32 pin connector (electronic module)

and probe or replace electronic module.

between electronics and probe.

CORRUPT PARAMTRS

Configuration parameters may

Check all configuration parameters 

(HART error code = 0x10)

have been lost.

and recalibrate if required. 

805 FAULT

Probe disconnected. 

Check white probe wire 

(Open)

(see page 2) and electronic module.

805 FAULT

Probe shorted. 

Check white probe wire 

(Shorted)

(see page 2) and probe insulation.

LEVEL

Unit is not calibrated. 

Enter both Low and High calibration 

(Uncal)

points.

ABV RNG

Measured capacitance is higher 

Consult factory. 

(Above range)

than 12,000 pF.

SFWR ERROR

Software error. 

Consult factory. 

(Software error)

ERROR MESSAGES – LCD version

Symptom

Problem

Solution

Содержание KOTRON SMART RF 805

Страница 1: ...R F Capacitance Level Measurement Installation and Operating Manual KOTRON SMART RF MODEL 805 TRANSMITTER...

Страница 2: ...and record the serial number for future reference when ordering parts MOUNTING Nameplate partnumber amplifier serial n tag n 2 cable entries one plugged M20 x 1 5 3 4 NPT or PG 13 5 Handtighten or us...

Страница 3: ...local current meter Ex Non Ex Ex Non Ex Ex Non Ex CAUTION ALWAYS check for proper grounding Improper grounding will cause malfunction of the unit CALIBRATION NOTE When connected to an approved barrie...

Страница 4: ...nt is the highest level from which the calibration is performed Hi Cal is measured from the end of the probe Lo Cal cm or inches Low Calibration point is the lowest level from which the cal ibration i...

Страница 5: ...single transmitter installation Fine tune the 4 mA point Attach a mA meter to the output If the output does not equal 4 0 mA adjust the value on the display to equal 4 00 mA Fine tune the 20 mA point...

Страница 6: ...oom Display Power Supply Current Meter 250 RL 450 CONNECTIONS Connection of your Hart communicator at power terminals and in wiring compartment at first junction box between unit and control room HART...

Страница 7: ...y HART software does not Contact manufacturer of your HART information e g Mfgs ID Device account for Mfgs ID s greater master software for upgrade This is a Serial etc but will not read any than 63 M...

Страница 8: ...3 003 Housing cover blind 316 SST Consult factory 5 Housing cover with glass 36 4410 001 Housing cover with glass 316 SST Consult factory 8 APPROVALS Agency Description ATEX II 1G EEx ia IIC T4 ambien...

Страница 9: ...Electronic Module Yes Yes Yes Yes Yes Yes Yes No No No No No No Display has Text No Reseat Boards Check Power Supply and Wiring Loop Resistance Wrong Correct Loop Resistance Start Good Display No Act...

Страница 10: ...lure to Operate with Correct Loop Inputs Display Working Yes No Retest Unit Good Display Key Board Responds Replace Electronic Module No Check Loop Current at Wiring Board Loop Current 22 4 0 mA Adjus...

Страница 11: ...heck Calibration Parameters Yes Yes Yes Corrupt Display Text Replace Electronic Module No Yes Replace Electronic Module Same Error Message Retest No Yes Active HART Analog Loop Correct Trim 4 20mA Che...

Страница 12: ...Material Aluminium A356T6 0 25 copper or 316 SST 1 4401 IP 65 Net and Gross Weight 2 70 kg net 3 20 kg gross Overall Dimensions H 214 mm 8 43 x W 111 mm 4 38 x D 188 mm 7 40 FUNCTIONAL PHYSICAL Descri...

Страница 13: ...e view Optional Mounting Flange 3 4 NPT 1 NPT 1G 1 BSP Optional Mounting Flange Optional Anchor Assembly Optional Weight 13 0 50 bare probe 16 0 625 insulated probe 5 0 1875 6 0 2500 75 2 95 34 1 32 1...

Страница 14: ...X II 1G EEx ia II C T6 A complete measuring system consists of a 1 Smart R F KOTRON 805 amplifier 2 KOTRON Probe a full range of rigid and flexible probes for conductive and non conductive media is av...

Страница 15: ...15...

Страница 16: ...Material Authorisation RMA form will be obtained from the factory It is mandatory that this form will be attached to each material returned This form is available through Magnetrol s local representat...

Отзывы: