MPS-122 

 

Setting swing door parameters – "MPS-Diag" 

 

 

58

 

 

5817,0011EN / Version 04 

 

Failed driver installation 

 

If installation was not successful, no port number is indicated for 
the connection "USB Serial Port". 

 

Fig. 26: Missing port number" if the installation has failed 

 

Choose another way of installing the driver. 

 See page 55, 

chapter 10.1.1 and page 56, chapter 10.1.2. 

 

10.2  Connecting laptop to control device MB-111 

Danger of crushing 

 

 CAUTION 

 

Danger of crushing! 

While the swing door is supplied with voltage, 
control commands can move the locking element. If 
these movements are made unexpectedly, they 
may cause crushing. 
–  Consider possible movements of the locking 

element for all work. 

 

 

 

The USB connection for the control unit MBC-111 is in the socket 
area of the swing door. 
1.  Loosen countersunk screw M6 of the cover disc. 
2.  Remove the cover disc and the O-ring. 
3.  4 Loosen the countersunk screws M8 and remove them. 
4.  Pull out outer tube and remove it. 
5.  Connect the laptop to the USB connection of the control unit 

MBC-111 via the USB connection. 

 

Содержание MPS-122

Страница 1: ...Operating Instructions Swing Door MPS 122 Doc ID 5817 0011EN Version 04...

Страница 2: ...on 04 Translation of the original operating instructions MAGNETIC Autocontrol GmbH Grienmatt 20 79650 Schopfheim Germany Tel 49 0 7622 695 5 Fax 49 0 7622 695 602 E Mail info ac magnetic com Internet...

Страница 3: ...4 1 Requirements 14 2 5 Personal protective equipment 15 2 6 Occupational safety and special dangers 15 2 6 1 Danger pictograms on the pedestrian barrier MPS 122 15 2 6 2 Hazard notes and occupational...

Страница 4: ...ings 42 8 Commissioning and settings 44 8 1 Safety 44 8 2 Switching the swing door on and off 45 8 3 Initial commissioning 46 8 4 Setting the home position and hold open time via button 47 8 4 1 Setti...

Страница 5: ...4 9 Teaching the three possible positions 64 10 4 10 Reset all parameters to factory settings 66 10 5 Firmware download 67 10 5 1 Firmware download using a mcp file 69 10 5 2 Firmware download using a...

Страница 6: ...Swing Door MPS 122 6 5817 0011EN Version 04...

Страница 7: ...local accident prevention regulations valid at the pedestrian barrier s area of application and general safety regulations have to be complied with Carefully read the operating instructions before sta...

Страница 8: ...s to an immediately dangerous situation which leads to death or severe injuries if it is not avoided WARNING The signal word WARNING points to a potentially dangerous situation which can lead to death...

Страница 9: ...ctual scope of supply may differ from the explanations and illustrations described in this manual in case of special designs if additional order options are made use of or due to latest technical chan...

Страница 10: ...he condition that the operating instructions are observed and that no inadmissible operations are carried out on the technical equipment and that the installation has suffered no mechanical damage MAG...

Страница 11: ...type code serial number etc before calling 1 9 EC Declarations of conformity EC Declarations of conformity pursuant to EC Machinery Directive 2006 42 EC Annex II refer to page 85 1 10 Environmental pr...

Страница 12: ...as little children older persons or persons with impairments separate access options must be provided The integrated MAGNETIC control units MBC and MMC are intended exclusively for controlling the MAG...

Страница 13: ...nce and cleaning of the pedestrian barrier ensure that all employees that are working at or with the pedestrian barrier have read and understood the operating instructions Furthermore the operator mus...

Страница 14: ...the pertinent regulations are able to carry out work assigned to them independently and to recognise potential hazards Electrical specialists are able due to their technical training knowledge and exp...

Страница 15: ...azards and to avoid dangerous situations 2 6 1 Danger pictograms on the pedestrian barrier MPS 122 The relevant dangerous areas on the pedestrian barriers can be identified by the following pictograms...

Страница 16: ...electrical specialists may carry out work on the electrical system Switch off power supply and secure against reactivation before performing any work Test for absence of voltage Never bypass or deact...

Страница 17: ...g the pedestrian barrier or heavy parts of it from the pallet should be done by a minimum of two people Heavy weight WARNING Lifting heavy loads The weight of heavy objects can severely injure a perso...

Страница 18: ...corners CAUTION Sharp edges and spiky corners Sharp edges and spiky corners can cause skin abrasions and cuts Work carefully near to sharp edges and spiky corners In case of doubt wear protective glo...

Страница 19: ...3 Technical data 3 1 Dimensions 3 1 1 Swing door in bracket version 5 480 390 30 159 D 50 B 1000 Mag00274b A A Fig 1 Dimensions for swing door in bracket version A Safety distances to avoid crushing...

Страница 20: ...rical connection Designation Unit MPS 122 230 V 50 Hz 1 115 V 60 Hz 1 Supply voltage V AC Hz 110 to 250 50 60 Hz Current consumption MPS in the resting position A 0 14 0 16 Power consumption MPS in th...

Страница 21: ...ge C 25 to 45 Storage temperature range C 30 to 70 Relative humidity r F max 95 non condensing Protection class IP 44 Table 2 Operating conditions 3 4 Weight Designation Unit MPS 122 Weight kg 40 Tabl...

Страница 22: ...unk screw M6 x16 2 Isolation sleeve 3 Top cover disc 4 O Ring 5 Countersunk screws M8 x 20 6 Outer tube 7 Edge profile with drive control units transformer 8 Disc screws M5 x 16 9 Cover 10 Threaded pi...

Страница 23: ...bidirectional operation with a 2 x 90 opening angle The opening angles may be changed between 10 and 300 by software Additional parameters such as speed hold open time etc can be changed by software...

Страница 24: ...d Install all fastening elements correctly Improper transport WARNING Improper transport The weight of the pedestrian barrier or its components can severely injure a person and cause severe crushing H...

Страница 25: ...pecialists only When unloading the packages and during in plant transportation always proceed with greatest care and caution Observe the dimensions of the pedestrian barrier Loading unloading as well...

Страница 26: ...the local situation Horizontal and even max deviations 2 mm m For plate lining ensure that the enclosed dowels securely grip in the foundation If required use longer tie anchors These tie anchors mus...

Страница 27: ...04 27 5 3 1 Foundation plan fixing and drilling plan 800 A 300 1 4 2 3 5 159 Mag00587a A 6 7 Fig 6 Foundation plan and fixing 1 Recessed head screw M8 x 80 2 Spring washer 3 Disc 4 Tie anchor with in...

Страница 28: ...nstallation 28 5817 0011EN Version 04 160 TK 105 70 14 3 3x 120 120 Mag00634 1 2 3 Fig 7 Drilling plan 1 Drilling hole Diameter 14 3 drilling depth 90 mm 2 Area for conduits 3 Alignment of edge profil...

Страница 29: ...S 1 Countersunk screw M6 x16 2 Isolation sleeve 3 Top cover disc 4 O Ring 5 Countersunk screws M8 x 20 6 Outer tube 7 Edge profile with drive control units transformer 8 Disc screws M5 x 16 9 Cover 10...

Страница 30: ...n placed The locking element is not installed yet Use enclosed attachment material The swing door is fastened on the foundation with 3 tie anchors NOTE For mounting the swing door on the foundation yo...

Страница 31: ...ended site so that the section in the housing as indicated in Fig 12 is about central in the direction of the desired home position Mark bores Put edge profile aside Setting bores The home position is...

Страница 32: ...x 10 Attach edge profile on the foundation with 3 screws spring washers and washers Observe that the lines are not damaged 11 Install cover 12 Install outer tube 13 Install the cover disc with the O...

Страница 33: ...cal system Switch off power supply and secure against reactivation before performing any work Test for absence of voltage Never bypass or deactivate fuses When replacing fuses observe the correct ampe...

Страница 34: ...ccording to the electrical circuit plan Only install and apply additional parts approved by MAGNETIC The electrical and electronically additional parts must be EMC verified and must not exceed the ind...

Страница 35: ...rerequisites The locking element is not installed yet DANGER Mortal danger by electric voltage 1 Disconnect supply line from power supply Ensure that the system is powered down Secure against reactiva...

Страница 36: ...7 0011EN Version 04 6 Connect control lines to the MBC 111 See page 37 chapter 6 4 7 Switch on swing door via 2 pin main switch 8 Check functions See page 44 chapter 8 9 Install cover 10 Install outer...

Страница 37: ...over all other inputs If several swing doors are to be opened at the same time using an external emergency STOP switch the inputs must be insulated with additional relays to avoid coupling of the volt...

Страница 38: ...for as long as the locking element is in the home position K3 Locking element in the left end position A permanent signal is delivered via this output for as long as the locking element is in the left...

Страница 39: ...ttachment for the locking element at the outer tube must be approximately centrally aligned in the direction of the home position The home position is the resting position of the locking element 1 Rem...

Страница 40: ...ng the right end stop 3 Tighten the bolt firmly Left end stop 4 Turn outer tube to the left until the stop screw touches the left end stop 5 Loosen the screw of the left end stop and move it until the...

Страница 41: ...ible disconnect the swing door from the voltage Consider possible movements of the locking element for all work 7 2 1 Mounting brackets Mag00625 1 3 2 4 Fig 18 Mounting brackets 1 Bracket 2 Outer tube...

Страница 42: ...ber inserts must be placed between glass wing and holder halves Mag00626a 1 2 3 4 5 6 5 Fig 19 Mounting glass wings 1 Glass wings 2 Outer tube 3 Screws M6 6 4 Front holder half 3 5 Rubber inserts 6 6...

Страница 43: ...Swing Door MPS 122 Mechanical settings and final installation 5817 0011EN Version 04 43 6 Put on the rubber inserts and holder halves 7 Tighten the screws M6 8 Secure the screws with Loctite...

Страница 44: ...al Switch off the power supply immediately in case of damage to the insulation and arrange repair Only qualified electricians may carry out work on the electrical system Switch off power supply and se...

Страница 45: ...othes Protective gloves Safety shoes 8 2 Switching the swing door on and off Fig 20 Switching the swing door on and off 1 2 pin main switch 1 Remove the cover disc with the O ring 2 Remove outer tube...

Страница 46: ...he software for the motor control unit MMC 120 may be loaded from the logic control unit first This process may take up to one minute Do not switch off the power supply during this time since this wou...

Страница 47: ...ver disc See page 22 Fig 3 Fig 21 Button for setting the home position and hold open time 8 4 1 Setting the home position Free movement path Ensure that the swing door can take up operation unhindered...

Страница 48: ...ins in the first end position 6 The locking element automatically swivels to the second end stop The buzzer emits a signal at a cycle of 1 Hz during the movement 7 The locking element briefly remains...

Страница 49: ...ld open time of one second Push the button 25 times for the maximum hold open time of 25 seconds 3 Wait for 5 seconds After 2 seconds the buzzer emits a signal at 6 Hz twice The number of pushes of th...

Страница 50: ...er gives warning signals Depending on whether a left or right swing door has been selected Homing takes place in different directions At a left swing door the locking element slowly swivels clockwise...

Страница 51: ...te brake is chosen for one or several positions the motor in the corresponding position is powered down and the brake is powered instead If no release has been given for one of the two opening directi...

Страница 52: ...and swivels on into the original direction again 9 5 2 Turning back during the movement The behaviour can be set via the parameter Brake options See page 61 chapter 10 4 2 Option Brake on if vandalis...

Страница 53: ...nt further in small steps If the vandalism attempt is cancelled the locking element swivels back to the home position Option Brake always off is activated The home position is only held by the motor t...

Страница 54: ...ithout additional programing for applications with an opening angle of 2 x 90 Functions and parameters can be changed on site via the programme MPS Diag The programme is included on a data carrier Add...

Страница 55: ...tomatic driver installation via setup assistant Using the driver from the internet 1 Plug the USB cable into the USB socket of the computer Windows 7 automatically recognises the newly connected hardw...

Страница 56: ...w Properties USB serial port is opened 3 Click the button Update driver The screen Update driver software appears 4 Select the option Automatically search for driver software Your operating system sea...

Страница 57: ...3 Entering the port number in the programme MPS Diag Successful driver installation 1 Click the icon Desktop 2 Select the menu field Properties The window Basic information is opened 3 Click the entr...

Страница 58: ...of crushing CAUTION Danger of crushing While the swing door is supplied with voltage control commands can move the locking element If these movements are made unexpectedly they may cause crushing Con...

Страница 59: ...Setupxxx exe and execute the instructions of the installation routine 3 A virtual COM port driver is installed during installation The port number of the serial interface is determined as follows Plug...

Страница 60: ...haviour when obstruction detected Hold open time Speeds Heating active while standing Programming the two end positions and the home position Resetting all parameters to factory settings 10 4 1 Versio...

Страница 61: ...he right swing door are presented 10 4 2 Brake activated not activated This option is used to inform the control if the brake is to be activated when one of the three positions is reached in case of v...

Страница 62: ...e or whether it starts to home immediately Fig 32 Select reset source 10 4 5 Stalled behaviour Behaviour when obstruction detected This selection point determines the behaviour of the swing door when...

Страница 63: ...eds 0 slow 1 medium or 2 fast The speed applies to regular operation If you have chosen more than 1 3 m for the parameter U bar size the parameter Speed only has the option 0 slow Observe that you alw...

Страница 64: ...However the three positions can be changed independently For this there is an input mask in MPS Diag Fig 37 Activate screen mask for adjusting the target positions Setting the target positions is a pr...

Страница 65: ...Setting swing door parameters MPS Diag 5817 0011EN Version 04 65 2 Adjust home position Fig 40 Adjust home position 3 Adjust left position Fig 41 Adjust left position 4 Adjust right position Fig 42 Ad...

Страница 66: ...10 Reset all parameters to factory settings This option can be used to restore the factory settings for all parameters 1 Open menu View and select the item Parameter Fig 44 Menu Parameter 2 The menu P...

Страница 67: ...e reset to factory settings Do you want to continue Fig 46 Safety confirmation Clicking Yes resets all parameters to factory settings Clicking No cancels the process 10 5 Firmware download To update t...

Страница 68: ...Fig 48 Menu Firmware update here no communication When communication to the control is present proceed as follows for downloading a new firmware version 3 Select the firmware file through the button...

Страница 69: ...ownload progress 2 When the download is completed perform voltage reset 10 5 2 Firmware download using an s file Only use firmware download using an s fule with a MBC111 control if the bootloader is n...

Страница 70: ...ecisely 7 When you have performed all steps click the OK button 8 When the connection to the bootloader is established the download will start The download progress is displayed in the status bar 9 Af...

Страница 71: ...r control device MMC 120 It verifies that the motor control device has the right software and the right software version for the MBC 111 application software If verification shows that the motor contr...

Страница 72: ...error codes right at the MBC 111 or MMC 120 is only possible after disassembly after removing the outer tube with the locking element Therefore the programme MPS Diag offers the possibility of reading...

Страница 73: ...with the locking element Therefore the programme MPS Diag offers the possibility of reading the status of the in and outputs through the serial interface NOTE The states of the DIP switches for param...

Страница 74: ...bypass or deactivate fuses When replacing fuses observe the correct amperage specification Keep moisture and dust away from live parts Moisture or dust may cause a short circuit Inappropriate cleanin...

Страница 75: ...age control commands can move the locking element If these movements are made unexpectedly they may cause crushing If possible disconnect the swing door from the voltage Consider possible movements of...

Страница 76: ...y and secure against restarting 2 Remove soiling appropriately Clean stainless steel surfaces and power coated parts regularly with a damp cloth and then dry off carefully Clean stainless steel surfac...

Страница 77: ...work To be carried out by Every 6 months Visual inspection of the outer swing door for damage Clean the housing and repair paint damage as necessary Specialist Check the function of the locking eleme...

Страница 78: ...tage Touching live parts can be lethal Damage to the insulation or to individual components can be lethal Switch off the power supply immediately in case of damage to the insulation and arrange repair...

Страница 79: ...e assembly site Loosely stacked or lying around components and tools are accident sources Only use original spare parts or spare parts approved of by MAGNETIC Procure spare parts from authorised deale...

Страница 80: ...ter a short break the error code is repeated The error code 02 is displayed as follows Two quick flashes After a short break the error code is repeated There will not be any slow flashing for the tens...

Страница 81: ...ved No 65 Error I C EEPROM No 66 Software fault No 70 to 7F Error when downloading the MMC 120 firmware No Table 8 Error code Self resetting errors are displayed for no more than 20 seconds if the err...

Страница 82: ...ed at both ends of the bus to prevent interference Setting the CAN address and termination is performed by DIP switches for both control devices The following DIP switch settings are correct Function...

Страница 83: ...ncorrect or defective spare parts can result in damage malfunctions or total failure and also impair safety Use only the manufacturer s original spare parts Procure spare parts from your dealer or dir...

Страница 84: ...rial types Non recyclable materials have to be disposed of in an environmental friendly manner Decommissioning disassembly and disposal of the pedestrian barrier may only be carried out by specialised...

Страница 85: ......

Страница 86: ...Swing Door MPS 122 Appendix 86 5817 0011EN Version 04 16 Appendix 16 1 Electric circuit diagram The electric circuit diagram is supplied as a separate document...

Страница 87: ...40 Environmental protection 11 Error codes 80 F Firmware download 69 Fixing 27 Foundation 26 Foundation plan 27 Function 23 Function description 50 Function settings 60 G General 7 H Hazard notes 16 H...

Страница 88: ...allation 24 Maintenance 74 Malfunctions 78 Settings 44 Transport 24 Scope of delivery 10 Setting Hold open time via the button 48 Home position via the button 47 Spare parts 83 Specialised staff 14 Sp...

Страница 89: ...Swing Door MPS 122 5817 0011EN Version 04 89...

Страница 90: ...F10042001 MAGNETIC Autocontrol GmbH Grienmatt 20 79650 Schopfheim Germany Tel 49 7622 695 5 Fax 49 7622 695 602 e mail info ac magnetic com...

Отзывы: