Swing Door
MPS-122
Malfunctions
82
12.3 CAN
bus
addressing and termination
The MBC-111 logic controller and the MMC-120 motor controller
exchange data via a CAN bus line. The MMC-120 controllers must
have a fixed CAN address assigned to it. Additionally, a
termination resistor must be activated at both ends of the bus to
prevent interference.
Setting the CAN address and termination is performed by DIP
switches for both control devices.
The following DIP switch settings are correct:
Function
DIP switch
MBC-111
MMC-120
Termination 1
ON ON
CAN address
2 OFF
OFF
3 OFF
OFF
4 OFF
OFF
Table 9: Setting of the DIP switches
Fig. 58: DIP switch
CAN MBC-111
Fig. 59: DIP switch
CAN MMC-120
NOTE!
Wrong settings for the DIP switch can lead to the
swing doors not going into operation or to
malfunctions during operation.