25
5.3.6.
Master preset
By using the reference point of the measuring unit, the position can be reproduced
as an absolute value when the power is restarted.
The procedure for master preset is as follows.
1.
Set Reference Point Use Setting to ON with a ladder program, etc. and
set the master preset value.
This task can also be performed using the “Setting application for
Windows PC (MG80SettingTool.exe).”
(Use Ref point: ON; Ref point Preset: Master preset value)
2.
Pass through the reference point of the measuring unit.
When the reference point is detected, the “REF” LED of the MG80-CM
lights up.
3.
Align the measuring unit with the master work to be measured.
4.
Call the master value with a ladder program, etc. (Master Preset Call
Instruction command).
Restart the power and move the measuring unit past the reference point.
Absolute value from the Master preset position will be loaded.