18 (E)
5.2. Setting the IP address and the device name
Static IP address and device name settings must be made for both the main unit side
and the project side.
Both the main unit and project side settings are made using SIMATIC STEP 7.
5.2.1. Main unit side
Check the following items before making the settings.
・
The number of nodes switch of the X20BC00E3 should be set to “0x00” before
supplying power to the X20BC00E3.
・
The development computer and the X20BC00E3 should be connected.
1.
Start up SIMATIC STEP 7, expand “Online access” with “Project view”, further
expand the Ethernet interface on the side of the development computer
connected to the X20BC00E3, and double-click “Update accessible devices”.
Fig. 5-7 SIMATIC STEP 7 -- Setting the IP address and the device name (main unit
side) -- No.1
2.
If the X20BC00E3 is detected normally, “Accessible device [MAC Address]” will
be added. Expand “Accessible device [MAC Address]”, and double-click “Online
& diagnostics”.
Fig. 5-8 SIMATIC STEP 7 -- Setting the IP address and the device name (main unit
side) -- No.2