![Magnescale MG70-EI Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/magnescale/mg70-ei/mg70-ei_instruction-manual_3573803015.webp)
13 (E)
5.
Right-click “MainTask” on the existing project side, and select “Properties”.
Fig. 5-6 Logix Designer -- Reflection to an existing project -- No.4
6.
Select the “Program Schedule” tab in the Properties window, and arrange the
“Scheduled” items in order of “CopyInputData”, “MainProgram”,
“CopyOutputData”.
* Arrange the items so that the program that will use the MG70-EI I/O data is
located between “CopyInputData” and “CopyOutputData”.
When finished, click “OK”.
Fig. 5-7 Logix Designer -- Reflection to an existing project -- No.5