CONNECTIONS TO COMPUTER: 

 

Connect  the  appropriate  cable  from  your  computer  to  the  Control  Unit

s  DB9  connector  on  the  rear  panel.           

(A standard RS232 cable is sufficient to run the controller. Do not use a null cable.)

 

 

All computers have a 

Hyper  Terminal

” 

or equivalent capability for 

Talking

” 

to the control unit. To setup the 

Hyper  Terminal

” 

do  the  following:  Click  start,  programs,  accessories,  communications  and  then               

Hyper Terminal.

” 

 

 

The next screen you will see is called 

Connection  Description.

” 

It will ask you to enter a name  (IE. positioner) 

and choose an icon, then click OK. 

 

 

The next screen will read 

Connect To.

” 

Scroll to the last box and click on 

Connect Using.

” 

Choose 

 

direct  to 

Com 1 

(or whatever Com port you have available) and then click OK.

 

 

 

 

The final screen will have standard Port Settings. Change the port settings to the following and press OK.

 

Baud Rate

 

Bits

 

Stop Bits

 

Parity 

 

Handshake

 

9600

 

8

 

1

 

None

 

Present, not used

 

 

 

COMPUTER SOFTWARE CLARIFICATIONS:

 

 

Commands are one letter or two letter, one number codes followed by a digit. (n)

 

 

In many commands, the (n) may be any numeric and must be a 

“0” 

(zero) where specified in the Command.

 

 

All  commands  and  responses  MUST  terminate  with  ;  (semi

-

colon),  Commands  are  in 

bold

  for  clarity.  Parts       

enclosed in 

( ) 

are optional. 

 

 

There are no inter

-

character timeouts, sending 

;

 alone will: 

 

 

A. Stop Controller command motion

 

 

B. Clear the RX buffer

 

 

There are no controller initiated transmissions. 

 

 

STANDARD USER PROGRAM COMMANDS:

 

 

Bin ; 

= Poll controller for Status / Heading 

   

(Response = 

ID_Byte, Status_Byte, Heading;

” 

ID

-

BYTES=ASCII Char 0

-

9 or A

-

Z STATUS_BYTE=)

 

 

 

 

S = Stopped / Idle

 

 

R = Running (motor in motion)

 

 

C = Calibration in Process

 

 

O = Offline (Controller NOT in MODE 0)

 

 

E = Error

 

 

Heading in form of 

(

-

)xxx.y;

 

 

 

Stn; or ; 

Stops a computer or preset command.

 

 

APn(

-

)xxx(.y)<cr>; 

Sends controller to (

-

)xxx.y degrees if in Mode 0.

 

 

C1n;  

Recalibrate controller at the desired Limit Switch (either CCW/DWN or CW/UP) known location.

 

 

 

 

 

 

 

 

ADVANCED OPERATIONS / SOFTWARE COMMANDS

 

Содержание RC2800PRKX2SU

Страница 1: ...2 FEATURES The M2 RC2800PRKX2SUMC is our Mid Grade rack mount controller The RC2800PRKX2SUMC was developed for Commercial Grade AZ EL Pedestal Models AE1000 AE1000CB and AE1000CBW Also available for a...

Страница 2: ...and PROGRAM MODE details following this section SPEED BUTTONS The SPEED buttons control the positioner s rate of speed in relative increments 1 is the slowest speed 9 is the fastest The top button in...

Страница 3: ...itioner unit The cable supplies pow er and data from the positioner Your ground connection is terminal 12 DISCONNECT THE AC POWER CORD WHEN CONNECTING CABLE LEADS RC2800PRKX2SUMC UNITS WITH HEATER If...

Страница 4: ...er commands This allows service or maintenance issues to be addressed without the danger of the service technician being injured While in Mode 1 the controller can be commanded with both the CCW DWN o...

Страница 5: ...he positioner to either the CCW DWN or CW UP limit switch location Note During Auto Cal the positioner WILL bypass the electronic limit to find either the CCW DWN or CW UP limit switch Rotator Locatio...

Страница 6: ...e controller for use by the Auto Cal Function Display Brightness Changes the brightness level of the LED Display Firmware Version Displays the current firmware from the controller when connected Read...

Страница 7: ...sed when less than 360 of travel is necessary with a southern exposure and avoids limits where most of the operations are being preformed Note the position of the Physical limit switches they are on t...

Страница 8: ...amount 10 SU Designation Azimuth N Center OVERVIEW This azimuth configuration may be used when 240 of travel is necessary with primarily a northern exposure and avoids limits where most of the operati...

Страница 9: ...10 UP ELECTRICAL LIMIT 100 ELEVATION AXIS OPTION 1 Characteristics Spectrum of use 0 to 180 plus Over travel amount 10 SU Designation Elevation 180 OVERVIEW This Elevation configuration is used as st...

Страница 10: ...___________________________________________________________________ __ WEST EAST EAST WEST AZIMUTH OPTION 3 AZIMUTH N Center AZIMUTH OPTION 4 AZIMUTH N Center NOTES____________________________________...

Страница 11: ...________________________________________ _________________________________________________________________________________________ _____________________________________________________________________...

Страница 12: ...be 3 You can adjust this by using the Min Speed slide bar in the setup utility The Min Speed is the minimum starting speed However please keep in mind The Min Speed must be set high enough to keep th...

Страница 13: ...ugh the limit switches and through to the positioner When the limit switch is activated it breaks the contact and stops the cur rent from continuing Reversing the positioner in the opposite direction...

Страница 14: ...he rear of the control unit Plug the AC cord into a reliable 115 VAC or 230 VAC source Switching power supplies are used that can operate from 86VAC to 240VAC CUSTOMER NOTE AREA CONNECTIONS AND START...

Страница 15: ...Red Black wires as shown Slide the prepared 2 Conductor Red Black 16AWG wire through the cord grip from the front of the panel Route the Red wire to position A as shown below Then route the Black wire...

Страница 16: ...ioner unit that DOES NOT have cord grips or wires running into it You will see the limit switches A B the limit arm C and limit screw D as pic tured to the right We have not installed the limit screw...

Страница 17: ...ave the choice of setting up either the CCW or CW hard limit as your Auto Cal location If most of your travel happens to be closer to the CW hard limit choose this in the setup utility If not we sugge...

Страница 18: ...rear of the control unit Then verify that the Pulse Divisor is set to the correct value for Elevation 13200 USING YOUR ELEVATION CONFIGURATION WORKSHEET 3 Using your Axis configuration worksheet inse...

Страница 19: ...its Parity Handshake 9600 8 1 None Present not used COMPUTER SOFTWARE CLARIFICATIONS Commands are one letter or two letter one number codes followed by a digit n In many commands the n may be any nume...

Страница 20: ...y Writes EE value yyy into X location The EE locations for X A Limit Switch Tenths of degrees from Initial Cal Heading that trips desired limit switch B Initial Cal Heading Heading to use as Limit Swi...

Страница 21: ...software This is more than 45 degrees CCW DWN from zero 90 when the pulse divider is at it s max of 50 000 We allow 90 degrees with the pulse divider that you are using now E3 Backup No Motion The PO...

Страница 22: ...432 8873 and we will help you trouble shoot the system If the above appears OK then the missing pulses maybe caused by a control cable problem or a damaged Positioner Again turn off the control unit a...

Страница 23: ...see if this wire is shorted to ground If not then the problem may be in the control unit The hexfet could be shorted or the motor drive chip could have failed allowing 10 volts to appear on the gate...

Страница 24: ...ct Some states or provinces do not allow the exclusion or limitation of liability for consequential or incidental damages so the above limitation may not apply In the event repair or replacement are n...

Отзывы: