Choose alarm functions.
ADDRESS
PARAMETER
RANGE
DEFAULT
257
CT input 1, Heater wire break alarm
0 : Disable
1 : Enable
0
263
CT input 1, SSR shortcircuit failure alarm
269
CT input 1, Overload alarm
513
CT input 2, Heater wire break alarm
519
CT input 2, SSR shortcircuit failure alarm
525
CT input 2, Overload alarm
• ALARM SETPOINT
Specify a threshold for each alarm.
ADDRESS
PARAMETER
RANGE
DEFAULT
258
CT input 1, Heater wire break alarm setpoint
0.0 to 600.0 A
0.0
264
CT input 1, SSR shortcircuit failure alarm setpoint
270
CT input 1, Overload alarm setpoint
514
CT input 2, Heater wire break alarm setpoint
520
CT input 2, SSR shortcircuit failure alarm setpoint
526
CT input 2, Overload alarm setpoint
• ALARM HYSTERESIS (DEADBAND)
Hysteresis, a deadband between ON point and OFF point, is used to prevent frequent ON/OFF operations (generally called
‘chattering’) of an alarm output device when the current fluctuates around the setpoint.
ADDRESS
PARAMETER
RANGE
DEFAULT
259
CT input 1, Heater wire break alarm hysteresis
0.0 to 99.9 A
0.0
265
CT input 1, SSR shortcircuit failure alarm hysteresis
271
CT input 1, Overload alarm hysteresis
515
CT input 2, Heater wire break alarm hysteresis
521
CT input 2, SSR shortcircuit failure alarm hysteresis
527
CT input 2, Overload alarm hysteresis
• ALARM LATCHING
Once an alarm is tripped, it is held when the alarm condition is cancelled.
Latched alarm is reset by turning the device’s power supply off or by a Modbus command.
ADDRESS
PARAMETER
RANGE
DEFAULT
260
CT input 1, Heater wire break alarm latching
0 : Disable
1 : Enable
0
266
CT input 1, SSR shortcircuit failure alarm latching
272
CT input 1, Overload alarm latching
516
CT input 2, Heater wire break alarm latching
522
CT input 2, SSR shortcircuit failure alarm latching
528
CT input 2, Overload alarm latching
• ALARM OUTPUT
Specify the output device for alarms.
When one of the control outputs is specified, be sure also to specify ‘Alarm OR’ or ‘Alarm AND’ with its output assignment.
With ‘Alarm OR’ setting, the output is provided if one or more alarms assigned to it are in true conditions. With ‘Alarm AND’
setting it is provided only if all alarms assigned to it are in true conditions.
ADDRESS
PARAMETER
RANGE
DEFAULT
261
CT input 1, Heater wire break alarm output
0 : Network only
1 : Control output 1
2 : Control output 2
3 : Control output 3
4 : Control output 4
0
267
CT input 1, SSR shortcircuit failure alarm output
273
CT input 1, Overload alarm output
517
CT input 2, Heater wire break alarm output
523
CT input 2, SSR shortcircuit failure alarm output
529
CT input 2, Overload alarm output