HEATING SENSITIVITY / COOLING SENSITIVITY
Sensitivity, a deadband between ON point and OFF point for heating/cooling control output, is used to prevent frequent ON/
OFF operations (generally called ‘chattering’) of a control output device when the PV fluctuates around the setpoint.
[Bank 1]
ADDRESS
PARAMETER
RANGE
DEFAULT
1168
Loop 1, Heating sensitivity
0.0 to 999.9
(decimal by input 1 decimal setting)
0.0
1169
Loop 1, Cooling sensitivity
1808
Loop 2, Heating sensitivity
0.0 to 999.9
(decimal by input 2 decimal setting)
0.0
1809
Loop 2, Cooling sensitivity
[Bank 2]
ADDRESS
PARAMETER
RANGE
DEFAULT
1328
Loop 1, Heating sensitivity
0.0 to 999.9
(decimal by input 1 decimal setting)
0.0
1329
Loop 1, Cooling sensitivity
1872
Loop 2, Heating sensitivity
0.0 to 999.9
(decimal by input 2 decimal setting)
0.0
1873
Loop 2, Cooling sensitivity
[Bank 3]
ADDRESS
PARAMETER
RANGE
DEFAULT
1488
Loop 1, Heating sensitivity
0.0 to 999.9
(decimal by input 1 decimal setting)
0.0
1489
Loop 1, Cooling sensitivity
1936
Loop 2, Heating sensitivity
0.0 to 999.9
(decimal by input 2 decimal setting)
0.0
1937
Loop 2, Cooling sensitivity
[Bank 4]
ADDRESS
PARAMETER
RANGE
DEFAULT
1648
Loop 1, Heating sensitivity
0.0 to 999.9
(decimal by input 1 decimal setting)
0.0
1649
Loop 1, Cooling sensitivity
2000
Loop 2, Heating sensitivity
0.0 to 999.9
(decimal by input 2 decimal setting)
0.0
2001
Loop 2, Cooling sensitivity