TC10EM
P. 24 / 43
EM-9581-B Rev.1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
BANK
The Controller has four sets of banks per loop. Temperature setpoint and PID and other parameters can be stored and
switched easily during operation by an external event input (Di) or via Modbus communication.
Bank 1 is used when there is no bank switching.
■
SP (SETPOINT VALUE)
Specify local SP.
CAUTION
Local SP bank is saved in the nonvolatile memory of the device.
If the SP bank is changed frequently during operation, the memory may reach its limit of writing, approx. 10
6
cycles
in a short time.
Use the ‘Setpoint Value Setting’ for frequent changes.
[Bank 1]
ADDRESS
PARAMETER
RANGE
DEFAULT
1153
Loop 1, SP (setpoint value)
-3200.0 to +3200.0
(decimal by input 1/2 decimal setting)
25.0
1793
Loop 2, SP (setpoint value)
[Bank 2]
ADDRESS
PARAMETER
RANGE
DEFAULT
1313
Loop 1, SP (setpoint value)
-3200.0 to +3200.0
(decimal by input 1/2 decimal setting)
25.0
1857
Loop 2, SP (setpoint value)
[Bank 3]
ADDRESS
PARAMETER
RANGE
DEFAULT
1473
Loop 1, SP (setpoint value)
-3200.0 to +3200.0
(decimal by input 1/2 decimal setting)
25.0
1921
Loop 2, SP (setpoint value)
[Bank 4]
ADDRESS
PARAMETER
RANGE
DEFAULT
1633
Loop 1, SP (setpoint value)
-3200.0 to +3200.0
(decimal by input 1/2 decimal setting)
25.0
1985
Loop 2, SP (setpoint value)
■
SP RAMP FALL RATE / SP RAMP RISE RATE
SP can be changed gradually in specified ramp rates when a new SP value is applied. SP ramp fall rate is applied with a
decreasing SP, while SP rise rate is with an increasing SP. Unit is “setting temperature/sec.”
The SP is instantly switched to a new value when ‘0.0’ is set.
The setting is valid for all SP value changes except at STOP status and in error status.
[Bank 1]
ADDRESS
PARAMETER
RANGE
DEFAULT
1154
Loop 1, SP ramp fall rate
0.0 to 3200.0 per second
(decimal by input 1 decimal setting)
0.0
1155
Loop 1, SP ramp rise rate
1794
Loop 2, SP ramp fall rate
0.0 to 3200.0 per second
(decimal by input 2 decimal setting)
0.0
1795
Loop 2, SP ramp rise rate
[Bank 2]
ADDRESS
PARAMETER
RANGE
DEFAULT
1314
Loop 1, SP ramp fall rate
0.0 to 3200.0 per second
(decimal by input 1 decimal setting)
0.0
1315
Loop 1, SP ramp rise rate
1858
Loop 2, SP ramp fall rate
0.0 to 3200.0 per second
(decimal by input 2 decimal setting)
0.0
1859
Loop 2, SP ramp rise rate
[Bank 3]
ADDRESS
PARAMETER
RANGE
DEFAULT
1474
Loop 1, SP ramp fall rate
0.0 to 3200.0 per second
(decimal by input 1 decimal setting)
0.0
1475
Loop 1, SP ramp rise rate
1922
Loop 2, SP ramp fall rate
0.0 to 3200.0 per second
(decimal by input 2 decimal setting)
0.0
1923
Loop 2, SP ramp rise rate
[Bank 4]
ADDRESS
PARAMETER
RANGE
DEFAULT
1634
Loop 1, SP ramp fall rate
0.0 to 3200.0 per second
(decimal by input 1 decimal setting)
0.0
1635
Loop 1, SP ramp rise rate
1986
Loop 2, SP ramp fall rate
0.0 to 3200.0 per second
(decimal by input 2 decimal setting)
0.0
1987
Loop 2, SP ramp rise rate